Skip to Content

Dry cooler BE-t-291HB1-B04 C

Dry cooler BE-t-291HB1-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-291HB1-B04 C

Heat rejection i
225.52 kW
Air flow
58,434 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 58,434 m³/h
External surface 634.6 m²
Inner volume 76.2 dm³
Fin materialAluminium
Net weight 693 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-291HB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
225.515 kW Fluid flow 39.11 m³/h Pressure drop 77.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
177.878 kW Fluid flow 30.85 m³/h Pressure drop 50.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 134.47 not rated not rated not rated not rated not rated
40 225.52 134.40 not rated not rated not rated not rated
45 313.99 224.55 134.32 not rated not rated not rated
50 401.59 312.21 223.70 134.29 not rated not rated
55 488.78 399.03 310.65 223.01 134.28 not rated
60 575.75 485.47 396.80 309.38 222.55 134.45

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 107.07 not rated not rated not rated not rated not rated
40 177.88 106.94 not rated not rated not rated not rated
45 246.48 176.99 106.83 not rated not rated not rated
50 314.33 244.91 176.21 106.74 not rated not rated
55 381.85 312.13 243.55 175.59 106.74 not rated
60 449.18 379.02 310.20 242.43 175.17 106.84

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 225.515 39.11 77.3
Low speed (Y) 177.878 30.85 50.6

Dimensions

Dimension drawing of BE-t-291HB1-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 4060 mm
F 1050 mm
G 4660 mm
E1 1830 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4660 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.