BE-2x191CC5-B04T C
224.49 kW
Defrost: None
Product code: BE-380AC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 63,842 m³/h |
|---|---|
| External surface | 955.1 m² |
| Inner volume | 142.3 dm³ |
| Fin material | Aluminium |
| Net weight | 908 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-380AC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 132.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 224.76 | 132.56 | not rated | not rated | not rated | not rated |
| 45 | 314.64 | 224.10 | 132.67 | not rated | not rated | not rated |
| 50 | 403.75 | 313.27 | 223.52 | 132.77 | not rated | not rated |
| 55 | 492.51 | 401.71 | 312.09 | 223.08 | 132.93 | not rated |
| 60 | 581.05 | 489.81 | 399.95 | 311.15 | 222.80 | 133.20 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 105.13 | not rated | not rated | not rated | not rated | not rated |
| 40 | 176.75 | 105.19 | not rated | not rated | not rated | not rated |
| 45 | 246.30 | 176.13 | 105.23 | not rated | not rated | not rated |
| 50 | 315.18 | 245.11 | 175.60 | 105.28 | not rated | not rated |
| 55 | 383.74 | 313.42 | 244.07 | 175.20 | 105.40 | not rated |
| 60 | 452.12 | 381.44 | 311.91 | 243.26 | 174.97 | 105.58 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 224.759 | 39.01 | 42.6 |
| Low speed (Y) | 176.745 | 30.66 | 27.7 |
| A | 1808 mm |
|---|---|
| B | 1150 mm |
| C | 4060 mm |
| F | 1050 mm |
| G | 4660 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.