Skip to Content

Dry cooler BE-2x191CC5-B04T C

Dry cooler BE-2x191CC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x191CC5-B04T C

Heat rejection i
224.49 kW
Air flow
59,298 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,298 m³/h
External surface 1,133.4 m²
Inner volume 177.0 dm³
Fin materialAluminium
Net weight 1,173 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x191CC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
224.493 kW Fluid flow 38.93 m³/h Pressure drop 72.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
177.871 kW Fluid flow 30.85 m³/h Pressure drop 47.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 134.86 not rated not rated not rated not rated not rated
40 224.49 134.60 not rated not rated not rated not rated
45 311.85 223.42 134.37 not rated not rated not rated
50 398.44 310.01 222.47 134.19 not rated not rated
55 484.68 395.88 308.41 221.69 134.09 not rated
60 570.72 481.39 393.62 307.08 221.14 134.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 107.79 not rated not rated not rated not rated not rated
40 177.87 107.49 not rated not rated not rated not rated
45 246.02 176.90 107.25 not rated not rated not rated
50 313.53 244.41 176.04 107.06 not rated not rated
55 380.75 311.30 243.00 175.34 106.94 not rated
60 447.80 377.91 309.35 241.83 174.84 106.96

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 224.493 38.93 72.3
Low speed (Y) 177.871 30.85 47.9

Dimensions

Dimension drawing of BE-2x191CC5-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 2850 mm
F 2330 mm
G 3450 mm
E1 2450 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3450 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.