BE-380AC5-B01 C
224.76 kW
Defrost: None
Product code: BE-2x191CC5-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 59,298 m³/h |
|---|---|
| External surface | 1,133.4 m² |
| Inner volume | 177.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,173 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x191CC5-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 134.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 224.49 | 134.60 | not rated | not rated | not rated | not rated |
| 45 | 311.85 | 223.42 | 134.37 | not rated | not rated | not rated |
| 50 | 398.44 | 310.01 | 222.47 | 134.19 | not rated | not rated |
| 55 | 484.68 | 395.88 | 308.41 | 221.69 | 134.09 | not rated |
| 60 | 570.72 | 481.39 | 393.62 | 307.08 | 221.14 | 134.10 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 107.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 177.87 | 107.49 | not rated | not rated | not rated | not rated |
| 45 | 246.02 | 176.90 | 107.25 | not rated | not rated | not rated |
| 50 | 313.53 | 244.41 | 176.04 | 107.06 | not rated | not rated |
| 55 | 380.75 | 311.30 | 243.00 | 175.34 | 106.94 | not rated |
| 60 | 447.80 | 377.91 | 309.35 | 241.83 | 174.84 | 106.96 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 224.493 | 38.93 | 72.3 |
| Low speed (Y) | 177.871 | 30.85 | 47.9 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 2850 mm |
| F | 2330 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.