BE-291DD5-B04 C
218.21 kW
Defrost: None
Product code: BE-t-2x191HB1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 57,904 m³/h |
|---|---|
| External surface | 581.3 m² |
| Inner volume | 79.7 dm³ |
| Fin material | Aluminium |
| Net weight | 932 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-t-2x191HB1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 130.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 219.11 | 130.32 | not rated | not rated | not rated | not rated |
| 45 | 305.45 | 218.25 | 130.27 | not rated | not rated | not rated |
| 50 | 390.97 | 303.84 | 217.49 | 130.26 | not rated | not rated |
| 55 | 476.11 | 388.63 | 302.42 | 216.89 | 130.32 | not rated |
| 60 | 561.02 | 473.05 | 386.58 | 301.27 | 216.49 | 130.48 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 104.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 173.19 | 103.93 | not rated | not rated | not rated | not rated |
| 45 | 240.28 | 172.38 | 103.81 | not rated | not rated | not rated |
| 50 | 306.67 | 238.84 | 171.68 | 103.76 | not rated | not rated |
| 55 | 372.73 | 304.63 | 237.59 | 171.12 | 103.78 | not rated |
| 60 | 438.62 | 370.10 | 302.85 | 236.58 | 170.76 | 103.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 219.110 | 38.00 | 93.4 |
| Low speed (Y) | 173.186 | 30.04 | 61.4 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 2250 mm |
| F | 2330 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.