Dry cooler BE-380BC1-B01 C

Dry cooler BE-380BC1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-380BC1-B01 C

Heat rejection i
221.42 kW
Air flow
62,564 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 62,564 m³/h
External surface 775.6 m²
Inner volume 89.9 dm³
Fin materialAluminium
Net weight 825 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 85.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-380BC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
221.415 kW Fluid flow 38.43 m³/h Pressure drop 106.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
172.557 kW Fluid flow 29.92 m³/h Pressure drop 68.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 131.70 not rated not rated not rated not rated not rated
40 221.42 131.71 not rated not rated not rated not rated
45 308.88 220.73 131.71 not rated not rated not rated
50 395.64 307.57 220.15 131.74 not rated not rated
55 482.07 393.74 306.46 219.69 131.86 not rated
60 568.31 479.58 392.11 305.60 219.45 132.07

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 103.52 not rated not rated not rated not rated not rated
40 172.56 103.50 not rated not rated not rated not rated
45 239.76 171.98 103.48 not rated not rated not rated
50 306.35 238.68 171.48 103.51 not rated not rated
55 372.66 304.79 237.76 171.13 103.57 not rated
60 438.82 370.63 303.46 237.07 170.92 103.71

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 221.415 38.43 106.7
Low speed (Y) 172.557 29.92 68.3

Dimensions

Dimension drawing of BE-380BC1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 3750 mm
F 1050 mm
G 4360 mm
E1 1130 mm
E2 1100 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4360 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.