Skip to Content

Dry cooler BE-t-2x191HB5-C04C C

Dry cooler BE-t-2x191HB5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x191HB5-C04C C

Heat rejection i
187.29 kW
Air flow
56,932 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 56,932 m³/h
External surface 402.9 m²
Inner volume 65.7 dm³
Fin materialAluminium
Net weight 819 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-2x191HB5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
187.291 kW Fluid flow 32.50 m³/h Pressure drop 95.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
150.388 kW Fluid flow 26.10 m³/h Pressure drop 64.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 109.76 not rated not rated not rated not rated not rated
40 187.29 109.92 not rated not rated not rated not rated
45 262.98 186.86 110.05 not rated not rated not rated
50 338.04 262.02 186.50 110.18 not rated not rated
55 412.83 336.58 261.18 186.21 110.34 not rated
60 487.47 410.87 335.30 260.53 186.07 110.58

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 88.87 not rated not rated not rated not rated not rated
40 150.39 88.96 not rated not rated not rated not rated
45 210.26 149.96 89.03 not rated not rated not rated
50 269.62 209.38 149.60 89.11 not rated not rated
55 328.73 268.30 208.62 149.30 89.23 not rated
60 387.70 326.99 267.17 208.03 149.16 89.41

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 187.291 32.50 95.9
Low speed (Y) 150.388 26.10 64.9

Dimensions

Dimension drawing of BE-t-2x191HB5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 2250 mm
F 2230 mm
G 2850 mm
E1 1850 mm
H 2500 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2250 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.