Skip to Content

Dry cooler BE-t-2x191HC1-C04C C

Dry cooler BE-t-2x191HC1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x191HC1-C04C C

Heat rejection i
228.88 kW
Air flow
54,927 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 54,927 m³/h
External surface 633.9 m²
Inner volume 80.4 dm³
Fin materialAluminium
Net weight 879 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-2x191HC1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
228.876 kW Fluid flow 39.69 m³/h Pressure drop 89.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
176.506 kW Fluid flow 30.61 m³/h Pressure drop 56.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 138.18 not rated not rated not rated not rated not rated
40 228.88 138.03 not rated not rated not rated not rated
45 316.72 227.78 137.89 not rated not rated not rated
50 403.60 314.78 226.84 137.81 not rated not rated
55 490.04 400.86 313.11 226.09 137.83 not rated
60 576.23 486.52 398.50 311.78 225.63 138.02

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 107.77 not rated not rated not rated not rated not rated
40 176.51 107.62 not rated not rated not rated not rated
45 242.89 175.60 107.48 not rated not rated not rated
50 308.50 241.33 174.82 107.40 not rated not rated
55 373.75 306.33 239.99 174.22 107.42 not rated
60 438.81 370.98 304.46 238.95 173.86 107.58

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 228.876 39.69 89.1
Low speed (Y) 176.506 30.61 56.1

Dimensions

Dimension drawing of BE-t-2x191HC1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 2250 mm
F 2230 mm
G 2850 mm
E1 1850 mm
H 2500 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2250 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.