Skip to Content

Dry cooler BE-t-2x191HC5-B04T C

Dry cooler BE-t-2x191HC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x191HC5-B04T C

Heat rejection i
229.73 kW
Air flow
57,163 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 57,163 m³/h
External surface 656.2 m²
Inner volume 114.6 dm³
Fin materialAluminium
Net weight 974 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-t-2x191HC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
229.728 kW Fluid flow 39.84 m³/h Pressure drop 57.9 kPa
Heat rejection · Low speed (Y)
179.582 kW Fluid flow 31.14 m³/h Pressure drop 37.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 137.92 not rated not rated not rated not rated not rated
40 229.73 137.81 not rated not rated not rated not rated
45 318.78 228.67 137.66 not rated not rated not rated
50 406.91 316.89 227.74 137.59 not rated not rated
55 494.61 404.21 315.24 227.01 137.62 not rated
60 582.07 491.13 401.87 313.90 226.53 137.79

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 108.87 not rated not rated not rated not rated not rated
40 179.58 108.73 not rated not rated not rated not rated
45 247.96 178.66 108.59 not rated not rated not rated
50 315.56 246.34 177.84 108.50 not rated not rated
55 382.81 313.30 244.94 177.19 108.48 not rated
60 449.87 379.92 311.33 243.80 176.76 108.61

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 229.728 39.84 57.9
Low speed (Y) 179.582 31.14 37.4

Dimensions

Dimension drawing of BE-t-2x191HC5-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 2250 mm
F 2330 mm
G 2850 mm
E1 1850 mm
H 2500 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2850 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.