Skip to Content

Dry cooler BE-t-2x280GB5-B01T C

Dry cooler BE-t-2x280GB5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x280GB5-B01T C

Heat rejection i
273.33 kW
Air flow
83,698 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 83,698 m³/h
External surface 601.9 m²
Inner volume 109.3 dm³
Fin materialAluminium
Net weight 1,247 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-t-2x280GB5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
273.332 kW Fluid flow 47.44 m³/h Pressure drop 52.0 kPa
Heat rejection · Low speed (Y)
216.512 kW Fluid flow 37.58 m³/h Pressure drop 34.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 158.50 not rated not rated not rated not rated not rated
40 273.33 159.03 not rated not rated not rated not rated
45 385.22 272.96 159.47 not rated not rated not rated
50 496.16 384.07 272.64 159.90 not rated not rated
55 606.65 494.26 383.08 272.45 160.34 not rated
60 716.90 604.03 492.63 382.33 272.43 160.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 126.66 not rated not rated not rated not rated not rated
40 216.51 127.05 not rated not rated not rated not rated
45 303.73 216.13 127.37 not rated not rated not rated
50 390.14 302.69 215.80 127.66 not rated not rated
55 476.15 388.48 301.81 215.50 127.98 not rated
60 561.93 473.89 387.06 301.06 215.41 128.39

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 273.332 47.44 52.0
Low speed (Y) 216.512 37.58 34.3

Dimensions

Dimension drawing of BE-t-2x280GB5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 2650 mm
F 2330 mm
G 3250 mm
E1 1150 mm
H 2900 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3250 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.