BE-t-2x280GB5-B01T C
273.33 kW
Defrost: None
Product code: BE-t-380HB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 66,424 m³/h |
|---|---|
| External surface | 951.8 m² |
| Inner volume | 117.7 dm³ |
| Fin material | Aluminium |
| Net weight | 992 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-380HB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 164.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 273.48 | 164.47 | not rated | not rated | not rated | not rated |
| 45 | 378.78 | 271.98 | 164.22 | not rated | not rated | not rated |
| 50 | 482.95 | 376.20 | 270.65 | 164.01 | not rated | not rated |
| 55 | 586.59 | 479.32 | 373.92 | 269.57 | 163.93 | not rated |
| 60 | 689.93 | 581.94 | 476.13 | 372.03 | 268.80 | 164.03 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 128.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 211.28 | 128.28 | not rated | not rated | not rated | not rated |
| 45 | 291.15 | 209.98 | 128.01 | not rated | not rated | not rated |
| 50 | 370.10 | 288.96 | 208.83 | 127.79 | not rated | not rated |
| 55 | 448.62 | 367.07 | 287.05 | 207.88 | 127.69 | not rated |
| 60 | 526.91 | 444.78 | 364.43 | 285.47 | 207.20 | 127.73 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 273.475 | 47.43 | 49.1 |
| Low speed (Y) | 211.279 | 36.65 | 31.0 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 5860 mm |
| F | 1050 mm |
| G | 6460 mm |
| E1 | 1830 mm |
| E2 | 1800 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 6460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.