Dry cooler BE-t-2x280HC5-B01T C

Dry cooler BE-t-2x280HC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x280HC5-B01T C

Heat rejection i
376.20 kW
Air flow
87,162 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 87,162 m³/h
External surface 1,313.2 m²
Inner volume 189.9 dm³
Fin materialAluminium
Net weight 1,607 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-t-2x280HC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
376.195 kW Fluid flow 65.23 m³/h Pressure drop 87.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
287.678 kW Fluid flow 49.90 m³/h Pressure drop 54.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 230.90 not rated not rated not rated not rated not rated
40 376.20 230.05 not rated not rated not rated not rated
45 517.17 373.74 229.27 not rated not rated not rated
50 656.71 513.23 371.56 228.65 not rated not rated
55 795.60 651.36 509.78 369.78 228.26 not rated
60 934.14 788.87 646.68 506.94 368.50 228.20

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 178.40 not rated not rated not rated not rated not rated
40 287.68 177.64 not rated not rated not rated not rated
45 393.50 285.61 176.95 not rated not rated not rated
50 498.22 390.27 283.80 176.41 not rated not rated
55 602.44 493.89 387.47 282.33 176.06 not rated
60 706.38 597.02 490.12 385.17 281.27 175.89

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 376.195 65.23 87.6
Low speed (Y) 287.678 49.90 54.4

Dimensions

Dimension drawing of BE-t-2x280HC5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 4050 mm
F 2330 mm
G 4650 mm
E1 1850 mm
H 4300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.