BE-t-2x280HC5-B01T C
376.20 kW
Defrost: None
Product code: BE-t-391HC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 86,003 m³/h |
|---|---|
| External surface | 1,269.1 m² |
| Inner volume | 148.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,096 kg |
| Quantity | 3 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 8,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-391HC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 229.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 376.10 | 228.87 | not rated | not rated | not rated | not rated |
| 45 | 517.77 | 373.82 | 228.39 | not rated | not rated | not rated |
| 50 | 657.79 | 513.96 | 371.82 | 228.01 | not rated | not rated |
| 55 | 797.05 | 652.52 | 510.63 | 370.21 | 227.86 | not rated |
| 60 | 935.88 | 790.36 | 647.94 | 507.93 | 369.10 | 228.00 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 178.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 289.74 | 178.13 | not rated | not rated | not rated | not rated |
| 45 | 396.78 | 287.80 | 177.66 | not rated | not rated | not rated |
| 50 | 502.51 | 393.62 | 286.10 | 177.30 | not rated | not rated |
| 55 | 607.66 | 498.21 | 390.88 | 284.74 | 177.11 | not rated |
| 60 | 712.48 | 602.25 | 494.49 | 388.67 | 283.80 | 177.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 376.098 | 65.23 | 56.5 |
| Low speed (Y) | 289.739 | 50.25 | 35.4 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 5860 mm |
| F | 1050 mm |
| G | 6460 mm |
| E1 | 1830 mm |
| E2 | 1800 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 6460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.