Skip to Content

Dry cooler BE-t-2x380GC1-B01T C

Dry cooler BE-t-2x380GC1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x380GC1-B01T C

Heat rejection i
506.36 kW
Air flow
119,775 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 119,775 m³/h
External surface 1,421.1 m²
Inner volume 191.9 dm³
Fin materialAluminium
Net weight 1,834 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-t-2x380GC1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
506.357 kW Fluid flow 87.81 m³/h Pressure drop 128.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
382.736 kW Fluid flow 66.38 m³/h Pressure drop 78.2 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 308.48 not rated not rated not rated not rated not rated
40 506.36 307.97 not rated not rated not rated not rated
45 698.34 504.00 307.57 not rated not rated not rated
50 888.35 694.31 502.02 307.32 not rated not rated
55 1077.45 882.72 690.90 500.53 307.37 not rated
60 1266.05 1070.26 877.96 688.29 499.70 307.75

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 235.97 not rated not rated not rated not rated not rated
40 382.74 235.45 not rated not rated not rated not rated
45 524.81 380.74 235.02 not rated not rated not rated
50 665.35 521.52 379.07 234.78 not rated not rated
55 805.20 660.83 518.76 377.84 234.77 not rated
60 944.66 799.48 657.04 516.67 377.16 235.12

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 506.357 87.81 128.4
Low speed (Y) 382.736 66.38 78.2

Dimensions

Dimension drawing of BE-t-2x380GC1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 3750 mm
F 2330 mm
G 4350 mm
E1 1150 mm
E2 1100 mm
H 4000 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4350 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.