BE-t-2x480GB5-B01C C
506.36 kW
Defrost: None
Product code: BE-t-2x380GC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 119,775 m³/h |
|---|---|
| External surface | 1,421.1 m² |
| Inner volume | 191.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,834 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-t-2x380GC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 308.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 506.36 | 307.97 | not rated | not rated | not rated | not rated |
| 45 | 698.34 | 504.00 | 307.57 | not rated | not rated | not rated |
| 50 | 888.35 | 694.31 | 502.02 | 307.32 | not rated | not rated |
| 55 | 1077.45 | 882.72 | 690.90 | 500.53 | 307.37 | not rated |
| 60 | 1266.05 | 1070.26 | 877.96 | 688.29 | 499.70 | 307.75 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 235.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 382.74 | 235.45 | not rated | not rated | not rated | not rated |
| 45 | 524.81 | 380.74 | 235.02 | not rated | not rated | not rated |
| 50 | 665.35 | 521.52 | 379.07 | 234.78 | not rated | not rated |
| 55 | 805.20 | 660.83 | 518.76 | 377.84 | 234.77 | not rated |
| 60 | 944.66 | 799.48 | 657.04 | 516.67 | 377.16 | 235.12 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 506.357 | 87.81 | 128.4 |
| Low speed (Y) | 382.736 | 66.38 | 78.2 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 3750 mm |
| F | 2330 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.