Dry cooler BE-t-2x380HB1-B01C C

Dry cooler BE-t-2x380HB1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x380HB1-B01C C

Heat rejection i
506.92 kW
Air flow
129,929 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 129,929 m³/h
External surface 1,472.1 m²
Inner volume 189.1 dm³
Fin materialAluminium
Net weight 1,895 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-t-2x380HB1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
506.919 kW Fluid flow 87.90 m³/h Pressure drop 72.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
393.970 kW Fluid flow 68.32 m³/h Pressure drop 46.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 302.68 not rated not rated not rated not rated not rated
40 506.92 302.53 not rated not rated not rated not rated
45 705.30 504.72 302.33 not rated not rated not rated
50 901.68 701.25 502.76 302.22 not rated not rated
55 1097.14 895.87 697.69 501.19 302.21 not rated
60 1292.08 1089.60 890.78 694.80 500.14 302.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 237.58 not rated not rated not rated not rated not rated
40 393.97 237.31 not rated not rated not rated not rated
45 545.35 391.99 237.05 not rated not rated not rated
50 695.08 541.86 390.26 236.88 not rated not rated
55 844.03 690.16 538.82 388.86 236.87 not rated
60 992.57 837.72 685.88 536.36 387.94 237.12

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 506.919 87.90 72.5
Low speed (Y) 393.970 68.32 46.2

Dimensions

Dimension drawing of BE-t-2x380HB1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 5850 mm
F 2230 mm
G 6450 mm
E1 1850 mm
E2 1800 mm
H 6100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.