Skip to Content

Dry cooler BE-t-2x380HB5-B01C C

Dry cooler BE-t-2x380HB5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x380HB5-B01C C

Heat rejection i
468.91 kW
Air flow
130,753 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 130,753 m³/h
External surface 1,247.0 m²
Inner volume 189.1 dm³
Fin materialAluminium
Net weight 1,861 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-t-2x380HB5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
468.907 kW Fluid flow 81.38 m³/h Pressure drop 63.1 kPa
Heat rejection · Low speed (Y)
369.004 kW Fluid flow 64.00 m³/h Pressure drop 41.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 277.07 not rated not rated not rated not rated not rated
40 468.91 277.21 not rated not rated not rated not rated
45 655.60 467.31 277.27 not rated not rated not rated
50 840.65 652.43 465.89 277.35 not rated not rated
55 1024.93 836.01 649.68 464.70 277.59 not rated
60 1208.77 1018.83 831.95 647.42 463.98 278.01

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 220.04 not rated not rated not rated not rated not rated
40 369.00 220.02 not rated not rated not rated not rated
45 513.64 367.50 219.97 not rated not rated not rated
50 656.82 510.84 366.19 219.96 not rated not rated
55 799.34 652.78 508.39 365.14 220.03 not rated
60 941.49 794.09 649.26 506.41 364.46 220.26

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 468.907 81.38 63.1
Low speed (Y) 369.004 64.00 41.1

Dimensions

Dimension drawing of BE-t-2x380HB5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 5850 mm
F 2230 mm
G 6450 mm
E1 1850 mm
E2 1800 mm
H 6100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.