Skip to Content

Dry cooler BE-2x480AB5-B01C C

Dry cooler BE-2x480AB5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480AB5-B01C C

Heat rejection i
467.38 kW
Air flow
167,732 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 167,732 m³/h
External surface 1,461.3 m²
Inner volume 223.5 dm³
Fin materialAluminium
Net weight 2,091 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x480AB5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
467.375 kW Fluid flow 81.12 m³/h Pressure drop 76.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
377.516 kW Fluid flow 65.51 m³/h Pressure drop 52.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 270.13 not rated not rated not rated not rated not rated
40 467.38 270.94 not rated not rated not rated not rated
45 660.59 467.04 271.64 not rated not rated not rated
50 852.49 659.20 466.75 272.29 not rated not rated
55 1043.83 850.09 658.02 466.63 272.96 not rated
60 1234.80 1040.43 848.04 657.17 466.75 273.80

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 219.88 not rated not rated not rated not rated not rated
40 377.52 220.46 not rated not rated not rated not rated
45 531.59 377.10 220.91 not rated not rated not rated
50 684.47 530.24 376.66 221.36 not rated not rated
55 836.83 682.25 528.99 376.40 221.87 not rated
60 988.87 833.75 680.23 528.08 376.39 222.53

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 467.375 81.12 76.9
Low speed (Y) 377.516 65.51 52.6

Dimensions

Dimension drawing of BE-2x480AB5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 5250 mm
F 2230 mm
G 5850 mm
E1 1250 mm
E2 2400 mm
H 5500 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5850 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.