BE-t-591GB1-B04 C
464.96 kW
Defrost: None
Product code: BE-2x380AD5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 122,354 m³/h |
|---|---|
| External surface | 2,125.1 m² |
| Inner volume | 310.4 dm³ |
| Fin material | Aluminium |
| Net weight | 2,113 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380AD5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 277.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 466.00 | 277.39 | not rated | not rated | not rated | not rated |
| 45 | 649.45 | 464.50 | 277.53 | not rated | not rated | not rated |
| 50 | 831.14 | 646.49 | 463.24 | 277.75 | not rated | not rated |
| 55 | 1011.98 | 826.75 | 643.95 | 462.31 | 278.13 | not rated |
| 60 | 1192.36 | 1006.21 | 823.00 | 642.00 | 461.84 | 278.68 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 216.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 359.68 | 216.31 | not rated | not rated | not rated | not rated |
| 45 | 498.65 | 358.39 | 216.38 | not rated | not rated | not rated |
| 50 | 636.12 | 496.19 | 357.32 | 216.53 | not rated | not rated |
| 55 | 772.89 | 632.54 | 494.12 | 356.56 | 216.83 | not rated |
| 60 | 909.29 | 768.24 | 629.53 | 492.56 | 356.21 | 217.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 465.998 | 80.82 | 45.1 |
| Low speed (Y) | 359.680 | 62.38 | 28.3 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| H | 4300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.