Product code: BE-t-2x380HC5-B01C C

Heat rejection i
530.61 kW
Air flow
128,384 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 128,384 m³/h
External surface 1,662.6 m²
Inner volume 269.7 dm³
Fin materialAluminium
Net weight 1,997 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-2x380HC5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
530.610 kW Fluid flow 92.02 m³/h Pressure drop 44.0 kPa
Heat rejection · Low speed (Y)
407.429 kW Fluid flow 70.67 m³/h Pressure drop 27.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 319.86 not rated not rated not rated not rated not rated
40 530.61 319.48 not rated not rated not rated not rated
45 734.64 527.91 319.11 not rated not rated not rated
50 936.45 729.91 525.54 318.86 not rated not rated
55 1137.23 929.78 725.78 523.66 318.82 not rated
60 1337.44 1128.67 923.98 722.43 522.38 319.15

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 248.19 not rated not rated not rated not rated not rated
40 407.43 247.79 not rated not rated not rated not rated
45 561.10 405.13 247.39 not rated not rated not rated
50 712.98 557.18 403.10 247.10 not rated not rated
55 864.03 707.53 553.76 401.48 247.03 not rated
60 1014.63 857.11 702.80 551.01 400.40 247.27

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 530.610 92.02 44.0
Low speed (Y) 407.429 70.67 27.5

Dimensions

Dimension drawing of BE-t-2x380HC5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 5850 mm
F 2230 mm
G 6450 mm
E1 1850 mm
E2 1800 mm
H 6100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.