BE-591AD1-B04 C
529.04 kW
Defrost: None
Product code: BE-t-2x380HC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 128,384 m³/h |
|---|---|
| External surface | 1,662.6 m² |
| Inner volume | 269.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,997 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x380HC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 319.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 530.61 | 319.48 | not rated | not rated | not rated | not rated |
| 45 | 734.64 | 527.91 | 319.11 | not rated | not rated | not rated |
| 50 | 936.45 | 729.91 | 525.54 | 318.86 | not rated | not rated |
| 55 | 1137.23 | 929.78 | 725.78 | 523.66 | 318.82 | not rated |
| 60 | 1337.44 | 1128.67 | 923.98 | 722.43 | 522.38 | 319.15 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 248.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 407.43 | 247.79 | not rated | not rated | not rated | not rated |
| 45 | 561.10 | 405.13 | 247.39 | not rated | not rated | not rated |
| 50 | 712.98 | 557.18 | 403.10 | 247.10 | not rated | not rated |
| 55 | 864.03 | 707.53 | 553.76 | 401.48 | 247.03 | not rated |
| 60 | 1014.63 | 857.11 | 702.80 | 551.01 | 400.40 | 247.27 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 530.610 | 92.02 | 44.0 |
| Low speed (Y) | 407.429 | 70.67 | 27.5 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5850 mm |
| F | 2230 mm |
| G | 6450 mm |
| E1 | 1850 mm |
| E2 | 1800 mm |
| H | 6100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.