Skip to Content

Dry cooler BE-2X480BC5-B01T C

Dry cooler BE-2X480BC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X480BC5-B01T C

Heat rejection i
528.82 kW
Air flow
166,151 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 166,151 m³/h
External surface 1,604.8 m²
Inner volume 236.7 dm³
Fin materialAluminium
Net weight 2,301 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2X480BC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
528.818 kW Fluid flow 91.78 m³/h Pressure drop 104.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
416.846 kW Fluid flow 72.34 m³/h Pressure drop 68.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 311.62 not rated not rated not rated not rated not rated
40 528.82 311.94 not rated not rated not rated not rated
45 741.09 527.71 312.23 not rated not rated not rated
50 951.78 738.70 526.78 312.53 not rated not rated
55 1161.72 948.15 736.67 526.12 312.96 not rated
60 1371.25 1156.87 945.05 735.15 525.89 313.61

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 247.47 not rated not rated not rated not rated not rated
40 416.85 247.68 not rated not rated not rated not rated
45 582.02 415.88 247.88 not rated not rated not rated
50 745.80 579.98 415.06 248.12 not rated not rated
55 908.99 742.74 578.23 414.52 248.48 not rated
60 1071.83 904.94 740.18 576.99 414.34 249.07

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 528.818 91.78 104.3
Low speed (Y) 416.846 72.34 68.3

Dimensions

Dimension drawing of BE-2X480BC5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 4850 mm
F 2330 mm
G 5450 mm
E1 1150 mm
E2 2200 mm
H 5100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5450 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.