Skip to Content

Dry cooler BE-t-2x491GC1-B04T C

Dry cooler BE-t-2x491GC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x491GC1-B04T C

Heat rejection i
837.54 kW
Air flow
210,487 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 210,487 m³/h
External surface 2,067.0 m²
Inner volume 292.6 dm³
Fin materialAluminium
Net weight 2,473 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.3 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-2x491GC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
837.536 kW Fluid flow 145.26 m³/h Pressure drop 69.1 kPa
Heat rejection · Low speed (Y)
642.763 kW Fluid flow 111.49 m³/h Pressure drop 43.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 498.87 not rated not rated not rated not rated not rated
40 837.54 499.42 not rated not rated not rated not rated
45 1165.77 834.90 499.89 not rated not rated not rated
50 1490.46 1160.36 832.69 500.32 not rated not rated
55 1813.49 1482.42 1155.80 831.13 501.23 not rated
60 2135.58 1802.88 1475.62 1152.37 830.52 502.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 387.30 not rated not rated not rated not rated not rated
40 642.76 387.65 not rated not rated not rated not rated
45 889.36 640.60 388.01 not rated not rated not rated
50 1133.03 885.08 638.85 388.47 not rated not rated
55 1375.34 1126.77 881.56 637.69 389.24 not rated
60 1616.89 1367.16 1121.59 879.03 637.34 390.50

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 837.536 145.26 69.1
Low speed (Y) 642.763 111.49 43.0

Dimensions

Dimension drawing of BE-t-2x491GC1-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 5250 mm
F 2330 mm
G 5850 mm
E1 1250 mm
E2 2400 mm
H 5500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.