BE-2x680EC5-B01C C
837.04 kW
Defrost: None
Product code: BE-t-2x580GC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 199,624 m³/h |
|---|---|
| External surface | 2,368.4 m² |
| Inner volume | 321.6 dm³ |
| Fin material | Aluminium |
| Net weight | 2,845 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x580GC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 506.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 837.16 | 505.85 | not rated | not rated | not rated | not rated |
| 45 | 1157.70 | 833.69 | 505.65 | not rated | not rated | not rated |
| 50 | 1474.72 | 1151.34 | 830.73 | 505.65 | not rated | not rated |
| 55 | 1790.10 | 1465.65 | 1145.97 | 828.55 | 506.06 | not rated |
| 60 | 2104.57 | 1778.39 | 1457.98 | 1141.88 | 827.41 | 506.97 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 387.58 | not rated | not rated | not rated | not rated | not rated |
| 40 | 633.42 | 387.17 | not rated | not rated | not rated | not rated |
| 45 | 870.75 | 630.41 | 386.83 | not rated | not rated | not rated |
| 50 | 1105.30 | 865.51 | 627.89 | 386.73 | not rated | not rated |
| 55 | 1338.57 | 1097.98 | 861.13 | 626.04 | 386.98 | not rated |
| 60 | 1571.15 | 1329.23 | 1091.84 | 857.83 | 625.09 | 387.78 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 837.162 | 145.17 | 77.2 |
| Low speed (Y) | 633.422 | 109.86 | 47.0 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 5950 mm |
| F | 2330 mm |
| G | 6550 mm |
| E1 | 1150 mm |
| E2 | 3300 mm |
| H | 6200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6550 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.