Dry cooler BE-t-2x580GC5-B01T C

Dry cooler BE-t-2x580GC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x580GC5-B01T C

Heat rejection i
786.80 kW
Air flow
202,626 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 202,626 m³/h
External surface 2,006.3 m²
Inner volume 321.6 dm³
Fin materialAluminium
Net weight 2,791 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 90.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-2x580GC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
786.796 kW Fluid flow 136.44 m³/h Pressure drop 69.2 kPa
Heat rejection · Low speed (Y)
604.798 kW Fluid flow 104.88 m³/h Pressure drop 43.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 469.86 not rated not rated not rated not rated not rated
40 786.80 470.01 not rated not rated not rated not rated
45 1094.74 784.10 470.11 not rated not rated not rated
50 1399.61 1089.48 781.78 470.31 not rated not rated
55 1703.07 1391.94 1085.01 780.07 470.75 not rated
60 2005.74 1693.04 1385.41 1081.57 779.19 471.73

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 365.01 not rated not rated not rated not rated not rated
40 604.80 365.04 not rated not rated not rated not rated
45 836.94 602.49 365.03 not rated not rated not rated
50 1066.55 832.64 600.55 365.19 not rated not rated
55 1295.00 1060.37 829.03 599.19 365.61 not rated
60 1522.81 1287.00 1055.18 826.32 598.54 366.46

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 786.796 136.44 69.2
Low speed (Y) 604.798 104.88 43.3

Dimensions

Dimension drawing of BE-t-2x580GC5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 5950 mm
F 2330 mm
G 6550 mm
E1 1150 mm
E2 3300 mm
H 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6550 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.