BE-2x580AD5-B01T C
784.25 kW
Defrost: None
Product code: BE-t-2x580GC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 202,626 m³/h |
|---|---|
| External surface | 2,006.3 m² |
| Inner volume | 321.6 dm³ |
| Fin material | Aluminium |
| Net weight | 2,791 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x580GC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 469.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 786.80 | 470.01 | not rated | not rated | not rated | not rated |
| 45 | 1094.74 | 784.10 | 470.11 | not rated | not rated | not rated |
| 50 | 1399.61 | 1089.48 | 781.78 | 470.31 | not rated | not rated |
| 55 | 1703.07 | 1391.94 | 1085.01 | 780.07 | 470.75 | not rated |
| 60 | 2005.74 | 1693.04 | 1385.41 | 1081.57 | 779.19 | 471.73 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 365.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 604.80 | 365.04 | not rated | not rated | not rated | not rated |
| 45 | 836.94 | 602.49 | 365.03 | not rated | not rated | not rated |
| 50 | 1066.55 | 832.64 | 600.55 | 365.19 | not rated | not rated |
| 55 | 1295.00 | 1060.37 | 829.03 | 599.19 | 365.61 | not rated |
| 60 | 1522.81 | 1287.00 | 1055.18 | 826.32 | 598.54 | 366.46 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 786.796 | 136.44 | 69.2 |
| Low speed (Y) | 604.798 | 104.88 | 43.3 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 5950 mm |
| F | 2330 mm |
| G | 6550 mm |
| E1 | 1150 mm |
| E2 | 3300 mm |
| H | 6200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6550 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.