BE-2x680BD5-B01T C
870.26 kW
Defrost: None
Product code: BE-t-2x680GB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 248,293 m³/h |
|---|---|
| External surface | 2,131.6 m² |
| Inner volume | 298.8 dm³ |
| Fin material | Aluminium |
| Net weight | 3,324 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 21,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x680GB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 498.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 870.42 | 501.14 | not rated | not rated | not rated | not rated |
| 45 | 1230.59 | 869.77 | 503.71 | not rated | not rated | not rated |
| 50 | 1587.01 | 1226.91 | 869.18 | 505.97 | not rated | not rated |
| 55 | 1941.53 | 1580.47 | 1223.75 | 868.91 | 508.21 | not rated |
| 60 | 2295.02 | 1932.29 | 1574.88 | 1221.40 | 869.19 | 510.70 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 393.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 680.97 | 395.92 | not rated | not rated | not rated | not rated |
| 45 | 957.70 | 680.13 | 397.88 | not rated | not rated | not rated |
| 50 | 1230.91 | 954.39 | 679.46 | 399.68 | not rated | not rated |
| 55 | 1502.48 | 1225.32 | 951.60 | 679.13 | 401.49 | not rated |
| 60 | 1773.14 | 1494.72 | 1220.61 | 949.59 | 679.38 | 403.52 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 870.418 | 151.06 | 31.8 |
| Low speed (Y) | 680.967 | 118.11 | 20.3 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 7050 mm |
| F | 2330 mm |
| G | 7650 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| E3 | 2200 mm |
| H | 7300 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.