- Catalogue
- Dry coolers
- BE (Dry)
BE (Dry)
- Refrigerants
- ETHYLENE GLYCOL 30%, PROPYLENE GLYCOL 30%, WATER
- Capacity
- 69.30–1727.54 kW
- Fans
- ⌀800, ⌀910 mm
- Max. working pressure
- 10 bar
Model nomenclature
How to read the model codes of this series, with an example.
-
A
Series BE = BE = V-type dry cooler.
-
B
Fin type (optional "t") — = absent: standard corrugated finst = t: louvered fins (high-efficiency fin surface)
-
C
Fan rows (optional "Nx") — Catalogue: "Fan Row no." (number before x/X). — = absent: 1 fan row2x = 2 fan rows
-
D
Number of fans per row — Digit 1-9; total fans = fan rows x this digit.
-
E
Fan diameter — Two digits = diameter / 10 (91 = Ø910). 80 = Ø800 mm91 = Ø910 mm
-
G
Coil tube rows (2nd dimensional letter) B = 3 tube rowsC = 4 tube rowsD = 5 tube rows
-
H
Fin spacing — Catalogue fin-spacing code. 1 = 2.1 mm5 = 2.5 mm
-
I
Generation code — Catalogue: "Generation Code". B = generation BC = generation C
-
J
Fan data (fan motor code) — Catalogue: "Fan Data". Two digits select the fan motor (supply, poles); the meaning is series-specific. 01 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)04 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
-
K
Delivery version (optional) — = absent: standardC = C: container delivery versionT = T: truck delivery version
| Model | Heat rejection [kW] i Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 % | Fans | Air flow [m³/h] | Variants |
|---|---|---|---|---|
| BE-2x980EC1-B01C C | 1329.76 kW | 18 × ⌀800 | 347,686 |
Variants (1) |
| BE-2x980ED5-B01C C | 1337.21 kW | 18 × ⌀800 | 340,089 |
Variants (1) |
| BE-2x891AC5-B04T C | 1338.27 kW | 16 × ⌀910 | 434,306 |
Variants (1) |
| BE-2x980EC5-B01T C | 1338.70 kW | 18 × ⌀800 | 366,906 |
Variants (1) |
| BE-2x791EC1-B04T C | 1352.48 kW | 14 × ⌀910 | 362,932 |
Variants (1) |
| BE-2X980AC1-B01T C | 1353.94 kW | 18 × ⌀800 | 371,930 |
Variants (1) |
| BE-2x980AD1-B01C C | 1357.96 kW | 18 × ⌀800 | 347,861 |
Variants (1) |
| BE-2x891EB1-B04T C | 1367.47 kW | 16 × ⌀910 | 431,939 |
Variants (1) |
| BE-2x980AD5-B01T C | 1373.48 kW | 18 × ⌀800 | 367,062 |
Variants (1) |
| BE-2x991AC5-C04C C | 1384.19 kW | 18 × ⌀910 | 467,227 |
Variants (1) |
| BE-2x980ED1-B01C C | 1388.78 kW | 18 × ⌀800 | 332,323 |
Variants (1) |
| BE-2x891EC1-C04C C | 1393.00 kW | 16 × ⌀910 | 391,254 |
Variants (1) |
| BE-2x991EB1-C04C C | 1412.32 kW | 18 × ⌀910 | 463,793 |
Variants (1) |
| BE-2x980EC1-B01T C | 1417.13 kW | 18 × ⌀800 | 361,906 |
Variants (1) |
| BE-2x991EB5-B04T C | 1422.39 kW | 18 × ⌀910 | 491,833 |
Variants (1) |
| BE-2x980ED5-B01T C | 1428.30 kW | 18 × ⌀800 | 355,706 |
Variants (1) |
| BE-2x891EC5-B04T C | 1432.74 kW | 16 × ⌀910 | 421,556 |
Variants (1) |
| BE-2x991AB1-B04T C | 1435.79 kW | 18 × ⌀910 | 497,764 |
Variants (1) |
| BE-2x891AC1-B04T C | 1442.81 kW | 16 × ⌀910 | 428,530 |
Variants (1) |
| BE-2x980AD1-B01T C | 1446.23 kW | 18 × ⌀800 | 362,060 |
Variants (1) |
| BE-2x991EC5-C04C C | 1478.17 kW | 18 × ⌀910 | 449,652 |
Variants (1) |
| BE-2x980ED1-B01T C | 1485.31 kW | 18 × ⌀800 | 349,595 |
Variants (1) |
| BE-2x991AC1-C04C C | 1495.03 kW | 18 × ⌀910 | 459,124 |
Variants (1) |
| BE-2x991AC5-B04T C | 1519.78 kW | 18 × ⌀910 | 488,594 |
Variants (1) |
| BE-2x891EC1-B04T C | 1526.99 kW | 16 × ⌀910 | 414,779 |
Variants (1) |
| BE-2x991EB1-B04T C | 1548.06 kW | 18 × ⌀910 | 485,932 |
Variants (1) |
| BE-2x991EC1-C04C C | 1576.41 kW | 18 × ⌀910 | 440,161 |
Variants (1) |
| BE-2x991EC5-B04T C | 1621.36 kW | 18 × ⌀910 | 474,250 |
Variants (1) |
| BE-2x991AC1-B04T C | 1638.27 kW | 18 × ⌀910 | 482,096 |
Variants (1) |
| BE-2x991EC1-B04T C | 1727.54 kW | 18 × ⌀910 | 466,627 |
Variants (1) |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
Downloads
- BE-2x980EC1-B01C C — product datasheet (PDF)
- BE-2x980ED5-B01C C — product datasheet (PDF)
- BE-2x891AC5-B04T C — product datasheet (PDF)
- BE-2x980EC5-B01T C — product datasheet (PDF)
- BE-2x791EC1-B04T C — product datasheet (PDF)
- BE-2X980AC1-B01T C — product datasheet (PDF)
- BE-2x980AD1-B01C C — product datasheet (PDF)
- BE-2x891EB1-B04T C — product datasheet (PDF)
- BE-2x980AD5-B01T C — product datasheet (PDF)
- BE-2x991AC5-C04C C — product datasheet (PDF)
- BE-2x980ED1-B01C C — product datasheet (PDF)
- BE-2x891EC1-C04C C — product datasheet (PDF)
- BE-2x991EB1-C04C C — product datasheet (PDF)
- BE-2x980EC1-B01T C — product datasheet (PDF)
- BE-2x991EB5-B04T C — product datasheet (PDF)
- BE-2x980ED5-B01T C — product datasheet (PDF)
- BE-2x891EC5-B04T C — product datasheet (PDF)
- BE-2x991AB1-B04T C — product datasheet (PDF)
- BE-2x891AC1-B04T C — product datasheet (PDF)
- BE-2x980AD1-B01T C — product datasheet (PDF)
- BE-2x991EC5-C04C C — product datasheet (PDF)
- BE-2x980ED1-B01T C — product datasheet (PDF)
- BE-2x991AC1-C04C C — product datasheet (PDF)
- BE-2x991AC5-B04T C — product datasheet (PDF)
- BE-2x891EC1-B04T C — product datasheet (PDF)
- BE-2x991EB1-B04T C — product datasheet (PDF)
- BE-2x991EC1-C04C C — product datasheet (PDF)
- BE-2x991EC5-B04T C — product datasheet (PDF)
- BE-2x991AC1-B04T C — product datasheet (PDF)
- BE-2x991EC1-B04T C — product datasheet (PDF)
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.