- Catalogue
- Dry coolers
- BE (Dry)
BE (Dry)
- Refrigerants
- ETHYLENE GLYCOL 30%, PROPYLENE GLYCOL 30%, WATER
- Capacity
- 69.30–1727.54 kW
- Fans
- ⌀800, ⌀910 mm
- Max. working pressure
- 10 bar
Model nomenclature
How to read the model codes of this series, with an example.
-
A
Series BE = BE = V-type dry cooler.
-
B
Fin type (optional "t") — = absent: standard corrugated finst = t: louvered fins (high-efficiency fin surface)
-
C
Fan rows (optional "Nx") — Catalogue: "Fan Row no." (number before x/X). — = absent: 1 fan row2x = 2 fan rows
-
D
Number of fans per row — Digit 1-9; total fans = fan rows x this digit.
-
E
Fan diameter — Two digits = diameter / 10 (91 = Ø910). 80 = Ø800 mm91 = Ø910 mm
-
G
Coil tube rows (2nd dimensional letter) B = 3 tube rowsC = 4 tube rowsD = 5 tube rows
-
H
Fin spacing — Catalogue fin-spacing code. 1 = 2.1 mm5 = 2.5 mm
-
I
Generation code — Catalogue: "Generation Code". B = generation BC = generation C
-
J
Fan data (fan motor code) — Catalogue: "Fan Data". Two digits select the fan motor (supply, poles); the meaning is series-specific. 01 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)04 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
-
K
Delivery version (optional) — = absent: standardC = C: container delivery versionT = T: truck delivery version
| Model | Heat rejection [kW] i Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 % | Fans | Air flow [m³/h] | Variants |
|---|---|---|---|---|
| BE-680BB1-B01 C | 371.17 kW | 6 × ⌀800 | 128,351 |
Variants (1)
|
| BE-2x291AC1-B04T C | 371.30 kW | 4 × ⌀910 | 107,133 |
Variants (1) |
| BE-580BD5-B01 C | 372.08 kW | 5 × ⌀800 | 102,986 |
Variants (1)
|
| BE-t-2x291GB1-B04T C | 372.30 kW | 4 × ⌀910 | 109,186 |
Variants (1) |
| BE-491BD5-B04 C | 372.54 kW | 4 × ⌀910 | 108,700 |
Variants (1)
|
| BE-t-2x291HB5-C04C C | 374.32 kW | 4 × ⌀910 | 113,864 |
Variants (1) |
| BE-391CD5-B04 C | 374.49 kW | 3 × ⌀910 | 88,838 |
Variants (1)
|
| BE-580EB1-B01 C | 374.51 kW | 5 × ⌀800 | 105,985 |
Variants (1)
|
| BE-2x380AB5-B01T C | 374.55 kW | 6 × ⌀800 | 128,543 |
Variants (1) |
| BE-t-391HC1-B04 C | 376.10 kW | 3 × ⌀910 | 86,003 |
Variants (1)
|
| BE-t-2x280HC5-B01T C | 376.20 kW | 4 × ⌀800 | 87,162 |
Variants (1) |
| BE-391FC1-B04 C | 377.24 kW | 3 × ⌀910 | 88,363 |
Variants (1)
|
| BE-2x280CC1-B01T C | 378.39 kW | 4 × ⌀800 | 89,178 |
Variants (1) |
| BE-t-2x280HC1-B01C C | 379.17 kW | 4 × ⌀800 | 84,889 |
Variants (1) |
| BE-2x391BB5-C04C C | 380.77 kW | 6 × ⌀910 | 163,489 |
Variants (1) |
| BE-480FC5-B01 C | 381.26 kW | 4 × ⌀800 | 89,413 |
Variants (1)
|
| BE-391FD5-B04 C | 381.46 kW | 3 × ⌀910 | 87,819 |
Variants (1)
|
| BE-2x380DB5-B01C C | 381.62 kW | 6 × ⌀800 | 132,199 |
Variants (1) |
| BE-t-2x291GC1-C04C C | 382.07 kW | 4 × ⌀910 | 99,487 |
Variants (1) |
| BE-t-2x380GB5-B01C C | 382.79 kW | 6 × ⌀800 | 121,596 |
Variants (1) |
| BE-2x280CD5-B01T C | 383.15 kW | 4 × ⌀800 | 88,797 |
Variants (1) |
| BE-2x380AB1-B01C C | 383.35 kW | 6 × ⌀800 | 124,409 |
Variants (1) |
| BE-2x291DC1-C04C C | 384.05 kW | 4 × ⌀910 | 112,095 |
Variants (1) |
| BE-t-491GB1-B04 C | 386.01 kW | 4 × ⌀910 | 110,815 |
Variants (1)
|
| BE-2x280CD1-B01C C | 386.28 kW | 4 × ⌀800 | 87,298 |
Variants (1) |
| BE-591AB5-B04 C | 386.33 kW | 5 × ⌀910 | 142,080 |
Variants (1)
|
| BE-2x291DC5-B04T C | 386.87 kW | 4 × ⌀910 | 116,072 |
Variants (1) |
| BE-480CC1-B01 C | 387.20 kW | 4 × ⌀800 | 89,743 |
Variants (1)
|
| BE-t-580GB1-B01 C | 389.20 kW | 5 × ⌀800 | 105,031 |
Variants (1)
|
| BE-491AC1-B04 C | 389.48 kW | 4 × ⌀910 | 109,602 |
Variants (1)
|
| BE-580EC5-B01 C | 390.40 kW | 5 × ⌀800 | 104,167 |
Variants (1)
|
| BE-391CD1-B04 C | 390.69 kW | 3 × ⌀910 | 88,377 |
Variants (1)
|
| BE-t-2x291GC5-B04T C | 391.61 kW | 4 × ⌀910 | 106,839 |
Variants (1) |
| BE-680AB5-B01 C | 392.32 kW | 6 × ⌀800 | 130,190 |
Variants (1)
|
| BE-2X380BC1-B01C C | 392.61 kW | 6 × ⌀800 | 118,484 |
Variants (1) |
| BE-580BD1-B01 C | 394.81 kW | 5 × ⌀800 | 101,704 |
Variants (1)
|
| BE-391FD1-B04 C | 395.08 kW | 3 × ⌀910 | 87,263 |
Variants (1)
|
| BE-2x291CB5-B04T C | 395.56 kW | 4 × ⌀910 | 119,940 |
Variants (1) |
| BE-580AC1-B01 C | 395.58 kW | 5 × ⌀800 | 105,392 |
Variants (1)
|
| BE-480CD5-B01 C | 395.85 kW | 4 × ⌀800 | 89,423 |
Variants (1)
|
| BE-2X380BC5-B01T C | 396.73 kW | 6 × ⌀800 | 124,613 |
Variants (1) |
| BE-2x291CB1-C04C C | 397.03 kW | 4 × ⌀910 | 117,770 |
Variants (1) |
| BE-t-2x280HC1-B01T C | 397.10 kW | 4 × ⌀800 | 86,612 |
Variants (1) |
| BE-491BD1-B04 C | 397.53 kW | 4 × ⌀910 | 107,286 |
Variants (1)
|
| BE-480FC1-B01 C | 397.65 kW | 4 × ⌀800 | 89,081 |
Variants (1)
|
| BE-2x280CD1-B01T C | 398.02 kW | 4 × ⌀800 | 88,400 |
Variants (1) |
| BE-480FD5-B01 C | 401.33 kW | 4 × ⌀800 | 88,688 |
Variants (1)
|
| BE-591BB1-B04 C | 401.35 kW | 5 × ⌀910 | 141,244 |
Variants (1)
|
| BE-491AD5-B04 C | 401.42 kW | 4 × ⌀910 | 108,242 |
Variants (1)
|
| BE-2X380AC5-B01C C | 403.33 kW | 6 × ⌀800 | 121,877 |
Variants (1) |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
Downloads
- BE-680BB1-B01 C — product datasheet (PDF)
- BE-2x291AC1-B04T C — product datasheet (PDF)
- BE-580BD5-B01 C — product datasheet (PDF)
- BE-t-2x291GB1-B04T C — product datasheet (PDF)
- BE-491BD5-B04 C — product datasheet (PDF)
- BE-t-2x291HB5-C04C C — product datasheet (PDF)
- BE-391CD5-B04 C — product datasheet (PDF)
- BE-580EB1-B01 C — product datasheet (PDF)
- BE-2x380AB5-B01T C — product datasheet (PDF)
- BE-t-391HC1-B04 C — product datasheet (PDF)
- BE-t-2x280HC5-B01T C — product datasheet (PDF)
- BE-391FC1-B04 C — product datasheet (PDF)
- BE-2x280CC1-B01T C — product datasheet (PDF)
- BE-t-2x280HC1-B01C C — product datasheet (PDF)
- BE-2x391BB5-C04C C — product datasheet (PDF)
- BE-480FC5-B01 C — product datasheet (PDF)
- BE-391FD5-B04 C — product datasheet (PDF)
- BE-2x380DB5-B01C C — product datasheet (PDF)
- BE-t-2x291GC1-C04C C — product datasheet (PDF)
- BE-t-2x380GB5-B01C C — product datasheet (PDF)
- BE-2x280CD5-B01T C — product datasheet (PDF)
- BE-2x380AB1-B01C C — product datasheet (PDF)
- BE-2x291DC1-C04C C — product datasheet (PDF)
- BE-t-491GB1-B04 C — product datasheet (PDF)
- BE-2x280CD1-B01C C — product datasheet (PDF)
- BE-591AB5-B04 C — product datasheet (PDF)
- BE-2x291DC5-B04T C — product datasheet (PDF)
- BE-480CC1-B01 C — product datasheet (PDF)
- BE-t-580GB1-B01 C — product datasheet (PDF)
- BE-491AC1-B04 C — product datasheet (PDF)
- BE-580EC5-B01 C — product datasheet (PDF)
- BE-391CD1-B04 C — product datasheet (PDF)
- BE-t-2x291GC5-B04T C — product datasheet (PDF)
- BE-680AB5-B01 C — product datasheet (PDF)
- BE-2X380BC1-B01C C — product datasheet (PDF)
- BE-580BD1-B01 C — product datasheet (PDF)
- BE-391FD1-B04 C — product datasheet (PDF)
- BE-2x291CB5-B04T C — product datasheet (PDF)
- BE-580AC1-B01 C — product datasheet (PDF)
- BE-480CD5-B01 C — product datasheet (PDF)
- BE-2X380BC5-B01T C — product datasheet (PDF)
- BE-2x291CB1-C04C C — product datasheet (PDF)
- BE-t-2x280HC1-B01T C — product datasheet (PDF)
- BE-491BD1-B04 C — product datasheet (PDF)
- BE-480FC1-B01 C — product datasheet (PDF)
- BE-2x280CD1-B01T C — product datasheet (PDF)
- BE-480FD5-B01 C — product datasheet (PDF)
- BE-591BB1-B04 C — product datasheet (PDF)
- BE-491AD5-B04 C — product datasheet (PDF)
- BE-2X380AC5-B01C C — product datasheet (PDF)
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.