Skip to Content

Oil cooler OA/OB-150AC1-A09 C

Oil cooler OA/OB-150AC1-A09 C
Illustrative photo

Producer: Karyer · Line: OA/OB (Oil Coolers)

Product code: OA/OB-150AC1-A09 C

Heat rejection i
16.83 kW
Air flow
6,994 m³/h
Fans
1 × ⌀500 mm

Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %

Data

Coil
Air flow 6,994 m³/h
External surface 60.3 m²
Inner volume 7.3 dm³
Fin materialAluminium
Net weight 101 kg
Fans
Quantity 1
Diameter 500 mm
Speed 1,330 rpm
Power 700 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 47.0 dB(A)
Sound power 78.3 dB(A)
Energy class E
Connections
Inlet Ø35
Outlet Ø35
Defrost
OA/OB-150AC1-A09 C None

Performance

Outlet 60 °C

Fluid inlet 60–90 °C (outlet = inlet − 20 K, at least 5 K above the air inlet); air inlet 25…50 °C.

B100 80 → 60 °C, air inlet 32 °C

Heat rejection · Single phase
16.829 kW Fluid flow 1.77 m³/h Pressure drop 38.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 20 K)

B100; rows: fluid inlet [°C], outlet = inlet − 20 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 20 K)
Fluid inlet [°C] \ air [°C] 253035404550
60 9.11 6.40 3.85 not rated not rated not rated
70 14.94 11.95 9.10 6.40 3.84 not rated
80 21.35 18.10 14.97 11.97 9.11 6.40
90 28.29 24.79 21.41 18.14 15.00 12.00

Nominal rating

Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 16.829 1.77 38.8

Dimensions

Dimension drawing of OA/OB-150AC1-A09 C
Dimension drawing
Dimensions as drawn
A 1090 mm
B 860 mm
C 850 mm
E1 900 mm
E 830 mm
D 280 mm
D1 320 mm
D2 420 mm
D3 1020 mm
D IN Ø35
D OUT Ø35
Overall [mm]
Length 1090 mm
Width 900 mm
Height 1020 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.