OA/OB-263AD1-A01 C
46.51 kW
Defrost: None
Product code: OA/OB-263AD5-A01 C
Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %
| Air flow | 16,601 m³/h |
|---|---|
| External surface | 197.0 m² |
| Inner volume | 27.4 dm³ |
| Fin material | Aluminium |
| Net weight | 234 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø54 |
| OA/OB-263AD5-A01 C | None |
|---|
Fluid inlet 60–90 °C (outlet = inlet − 20 K, at least 5 K above the air inlet); air inlet 25…50 °C.
B100 80 → 60 °C, air inlet 32 °C
B100; rows: fluid inlet [°C], outlet = inlet − 20 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 60 | 25.10 | 17.83 | 10.88 | not rated | not rated | not rated |
| 70 | 40.62 | 32.65 | 25.04 | 17.78 | 10.85 | not rated |
| 80 | 57.47 | 48.86 | 40.57 | 32.61 | 25.01 | 17.76 |
| 90 | 75.52 | 66.34 | 57.43 | 48.84 | 40.55 | 32.61 |
Nominal conditions: oil 80 → 60 °C, air inlet 32 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 45.504 | 4.78 | 29.1 |
| A | 2210 mm |
|---|---|
| B | 1860 mm |
| C | 1150 mm |
| E1 | 1200 mm |
| E | 1830 mm |
| D | 310 mm |
| D1 | 370 mm |
| D2 | 435 mm |
| D3 | 1035 mm |
| D IN | Ø54 |
| D OUT | Ø54 |
| Length | 2210 mm |
|---|---|
| Width | 1200 mm |
| Height | 1035 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.