BSCR-2N-Q5-33.1Y-F-B
10.05 kW
Defrost: None
Product code: BSCR-2N-Q5-33.1Y-F-C
Nominal conditions: evaporating -35 °C, condensing 40 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Low temperature (LT) |
|---|---|
| Compressors | 2 × semi-hermetic reciprocating compressors |
| Liquid receiver | 45 l |
| Net weight | 355 kg |
| Max. current | 28.8 A |
|---|---|
| Starting current | 77.5 A |
| Suction | 1"5/8 |
|---|---|
| Liquid | 5/8" |
| Discharge | 1"1/8 |
| L / W / H | 666/402/1137 mm |
|---|---|
| Weight | 60 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -35 °C, condensing 40 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -35 | 40 | 10.05 | 8.14 | 1.23 | 14.4 |
| -35 | 45 | 8.87 | 8.26 | 1.07 | 14.6 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -45 | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 8.39 | 11.53 | 15.39 | 20.07 | 25.67 | 32.31 | 40.07 | 49.06 | 59.38 |
| 25 | 7.46 | 10.37 | 13.95 | 18.29 | 23.49 | 29.67 | 36.92 | 45.36 | 55.07 |
| 30 | 6.58 | 9.28 | 12.58 | 16.58 | 21.40 | 27.12 | 33.87 | 41.75 | 50.86 |
| 35 | 5.76 | 8.25 | 11.28 | 14.96 | 19.38 | 24.66 | 30.91 | 38.24 | 46.75 |
| 40 | 5.01 | 7.28 | 10.05 | 13.40 | 17.44 | 22.28 | 28.04 | 34.82 | 42.75 |
| 45 | 4.30 | 6.37 | 8.88 | 11.91 | 15.57 | 19.99 | 25.25 | 31.50 | not rated |
| 50 | not rated | 5.51 | 7.76 | 10.48 | 13.78 | 17.77 | 22.56 | not rated | not rated |
| 55 | not rated | not rated | not rated | not rated | 12.06 | 15.63 | 19.95 | not rated | not rated |
| Tc \ Te [°C] | -45 | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 5.62 | 6.51 | 7.44 | 8.35 | 9.19 | 9.91 | 10.46 | 10.79 | 10.84 |
| 25 | 5.69 | 6.65 | 7.67 | 8.71 | 9.72 | 10.64 | 11.42 | 12.02 | 12.38 |
| 30 | 5.74 | 6.75 | 7.86 | 9.02 | 10.18 | 11.29 | 12.30 | 13.16 | 13.81 |
| 35 | 5.77 | 6.82 | 8.01 | 9.29 | 10.60 | 11.89 | 13.11 | 14.22 | 15.16 |
| 40 | 5.79 | 6.88 | 8.14 | 9.52 | 10.97 | 12.44 | 13.87 | 15.22 | 16.43 |
| 45 | 5.82 | 6.94 | 8.26 | 9.74 | 11.32 | 12.95 | 14.58 | 16.17 | not rated |
| 50 | not rated | 7.02 | 8.39 | 9.95 | 11.65 | 13.44 | 15.26 | not rated | not rated |
| 55 | not rated | not rated | not rated | not rated | 11.99 | 13.92 | 15.93 | not rated | not rated |
| Tc \ Te [°C] | -45 | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 |
|---|---|---|---|---|---|---|---|---|---|
| 20 | 1.49 | 1.77 | 2.07 | 2.40 | 2.79 | 3.26 | 3.83 | 4.55 | 5.48 |
| 25 | 1.31 | 1.56 | 1.82 | 2.10 | 2.42 | 2.79 | 3.23 | 3.77 | 4.45 |
| 30 | 1.15 | 1.37 | 1.60 | 1.84 | 2.10 | 2.40 | 2.75 | 3.17 | 3.68 |
| 35 | 1.00 | 1.21 | 1.41 | 1.61 | 1.83 | 2.07 | 2.36 | 2.69 | 3.08 |
| 40 | 0.86 | 1.06 | 1.23 | 1.41 | 1.59 | 1.79 | 2.02 | 2.29 | 2.60 |
| 45 | 0.74 | 0.92 | 1.07 | 1.22 | 1.38 | 1.54 | 1.73 | 1.95 | not rated |
| 50 | not rated | 0.79 | 0.92 | 1.05 | 1.18 | 1.32 | 1.48 | not rated | not rated |
| 55 | not rated | not rated | not rated | not rated | 1.01 | 1.12 | 1.25 | not rated | not rated |
| L | 1310 mm |
|---|---|
| P | 825 mm |
| H | 1255 mm |