BSCR-2P-B2-10.1Y-F-C
9.16 kW
Defrost: None
Product code: BSCR-2P-B1.5-9.1Y-F-C
Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Medium temperature (MT) |
|---|---|
| Compressors | 2 × semi-hermetic reciprocating compressors |
| Liquid receiver | 45 l |
| Net weight | 255 kg |
| Max. current | 11.8 A |
|---|---|
| Starting current | 32.7 A |
| Suction | 1"1/8 |
|---|---|
| Liquid | 5/8" |
| Discharge | 1"1/8 |
| L / W / H | 666/402/1137 mm |
|---|---|
| Weight | 60 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -10 | 40 | 9.13 | 4.14 | 2.21 | 8.5 |
| -10 | 45 | 8.19 | 4.34 | 1.89 | 8.7 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 2.72 | 3.63 | 4.79 | 6.24 | 8.01 | 10.15 | 12.68 | 15.64 | 19.07 | not rated |
| 25 | 2.50 | 3.34 | 4.42 | 5.78 | 7.44 | 9.44 | 11.83 | 14.63 | 17.88 | 21.61 |
| 30 | 2.26 | 3.04 | 4.05 | 5.30 | 6.84 | 8.71 | 10.95 | 13.59 | 16.67 | 20.21 |
| 35 | 2.03 | 2.74 | 3.66 | 4.81 | 6.23 | 7.97 | 10.05 | 12.52 | 15.42 | 18.77 |
| 40 | 1.79 | 2.44 | 3.27 | 4.31 | 5.61 | 7.20 | 9.13 | 11.43 | 14.14 | 17.31 |
| 45 | 1.56 | 2.14 | 2.87 | 3.81 | 4.98 | 6.43 | 8.19 | 10.32 | 12.85 | 15.82 |
| 50 | 1.34 | 1.84 | 2.49 | 3.31 | 4.35 | 5.65 | 7.25 | 9.20 | 11.54 | 14.31 |
| 55 | not rated | not rated | 2.11 | 2.82 | 3.72 | 4.87 | 6.31 | 8.07 | 10.22 | 12.80 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 1.93 | 2.14 | 2.36 | 2.57 | 2.76 | 2.93 | 3.06 | 3.15 | 3.18 | not rated |
| 25 | 1.99 | 2.23 | 2.47 | 2.72 | 2.96 | 3.18 | 3.37 | 3.52 | 3.63 | 3.67 |
| 30 | 2.05 | 2.30 | 2.57 | 2.85 | 3.13 | 3.40 | 3.65 | 3.87 | 4.04 | 4.17 |
| 35 | 2.10 | 2.37 | 2.66 | 2.97 | 3.29 | 3.61 | 3.91 | 4.19 | 4.43 | 4.63 |
| 40 | 2.14 | 2.42 | 2.74 | 3.07 | 3.43 | 3.79 | 4.14 | 4.47 | 4.78 | 5.06 |
| 45 | 2.17 | 2.46 | 2.80 | 3.16 | 3.54 | 3.94 | 4.34 | 4.73 | 5.11 | 5.45 |
| 50 | 2.20 | 2.50 | 2.84 | 3.23 | 3.64 | 4.07 | 4.52 | 4.96 | 5.39 | 5.81 |
| 55 | not rated | not rated | 2.87 | 3.27 | 3.71 | 4.18 | 4.67 | 5.16 | 5.65 | 6.13 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 1.41 | 1.70 | 2.03 | 2.43 | 2.90 | 3.46 | 4.14 | 4.97 | 6.00 | not rated |
| 25 | 1.25 | 1.50 | 1.79 | 2.12 | 2.51 | 2.97 | 3.51 | 4.16 | 4.93 | 5.89 |
| 30 | 1.10 | 1.32 | 1.57 | 1.86 | 2.18 | 2.56 | 3.00 | 3.51 | 4.12 | 4.85 |
| 35 | 0.97 | 1.16 | 1.37 | 1.62 | 1.89 | 2.21 | 2.57 | 2.99 | 3.48 | 4.05 |
| 40 | 0.84 | 1.01 | 1.19 | 1.40 | 1.64 | 1.90 | 2.21 | 2.55 | 2.96 | 3.42 |
| 45 | 0.72 | 0.87 | 1.03 | 1.21 | 1.41 | 1.63 | 1.89 | 2.18 | 2.52 | 2.90 |
| 50 | 0.61 | 0.74 | 0.88 | 1.03 | 1.20 | 1.39 | 1.61 | 1.85 | 2.14 | 2.46 |
| 55 | not rated | not rated | 0.73 | 0.86 | 1.00 | 1.17 | 1.35 | 1.57 | 1.81 | 2.09 |
| L | 1310 mm |
|---|---|
| P | 825 mm |
| H | 1225 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.