BHSR-5P-ZB114
125.60 kW
Defrost: None
Product code: BHSR-6P-ZB95
Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Medium temperature (MT) |
|---|---|
| Compressors | 6 × scroll compressors |
| Liquid receiver | 150 l |
| Net weight | 1,040 kg |
| Max. current | 138.0 A |
|---|---|
| Starting current | 255.0 A |
| Suction | 4"1/8 |
|---|---|
| Liquid | 1"5/8 |
| Discharge | 2"1/8 |
| L / W / H | 790/538/1605 mm |
|---|---|
| Weight | 150 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -10 | 40 | 140.20 | 56.30 | 2.49 | 105.7 |
| -10 | 45 | 127.00 | 63.00 | 2.02 | 115.2 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|
| 20 | 98.10 | 122.60 | 151.50 | 185.10 | 224.10 | 268.80 | not rated |
| 25 | 91.60 | 115.20 | 142.80 | 174.90 | 211.90 | 254.30 | 302.40 |
| 30 | 84.30 | 107.20 | 133.50 | 164.00 | 199.10 | 239.30 | 284.90 |
| 35 | 76.20 | 98.30 | 123.50 | 152.50 | 185.70 | 223.70 | 266.90 |
| 40 | 67.20 | 88.60 | 112.70 | 140.20 | 171.60 | 207.50 | 248.30 |
| 45 | 57.00 | 77.90 | 101.00 | 127.00 | 156.70 | 190.50 | 228.90 |
| 50 | not rated | 66.00 | 88.20 | 112.90 | 140.90 | 172.60 | 208.80 |
| 55 | not rated | not rated | 74.40 | 97.80 | 124.10 | 153.90 | 187.90 |
| Tc \ Te [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|
| 20 | 34.90 | 35.60 | 36.40 | 37.40 | 38.30 | 39.10 | not rated |
| 25 | 39.10 | 39.60 | 40.30 | 41.20 | 42.10 | 43.00 | 43.80 |
| 30 | 44.00 | 44.30 | 44.80 | 45.60 | 46.40 | 47.30 | 48.20 |
| 35 | 49.80 | 49.70 | 50.00 | 50.50 | 51.30 | 52.10 | 53.00 |
| 40 | 56.60 | 56.10 | 56.00 | 56.30 | 56.80 | 57.50 | 58.30 |
| 45 | 64.40 | 63.50 | 63.00 | 63.00 | 63.30 | 63.80 | 64.40 |
| 50 | not rated | 72.10 | 71.20 | 70.70 | 70.70 | 70.90 | 71.30 |
| 55 | not rated | not rated | 80.60 | 79.70 | 79.20 | 79.10 | 79.30 |
| Tc \ Te [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|
| 20 | 2.81 | 3.44 | 4.16 | 4.95 | 5.85 | 6.87 | not rated |
| 25 | 2.34 | 2.91 | 3.54 | 4.25 | 5.03 | 5.91 | 6.90 |
| 30 | 1.92 | 2.42 | 2.98 | 3.60 | 4.29 | 5.06 | 5.91 |
| 35 | 1.53 | 1.98 | 2.47 | 3.02 | 3.62 | 4.29 | 5.04 |
| 40 | 1.19 | 1.58 | 2.01 | 2.49 | 3.02 | 3.61 | 4.26 |
| 45 | 0.89 | 1.23 | 1.60 | 2.02 | 2.48 | 2.99 | 3.55 |
| 50 | not rated | 0.92 | 1.24 | 1.60 | 1.99 | 2.43 | 2.93 |
| 55 | not rated | not rated | 0.92 | 1.23 | 1.57 | 1.95 | 2.37 |
| Length | 3715 mm |
|---|---|
| Width | 1000 mm |
| Height | 1500 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.