EA-DA-x-163BE7-B27 C
10.04 kW
Defrost: None
Product code: EA-DA-335BE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,117 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 38.0 m² |
| Inner volume | 14.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 104 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-DA-335BE7-C21 C | None |
|---|---|
| EA-DA-335BE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.80 | 4.16 | 4.49 | 4.77 | 4.96 | 5.07 | 5.09 | 5.24 | 5.58 | 6.07 | 5.93 | 5.87 | 5.80 | 5.69 |
| 5 | ≈ 4.56 | 5.08 | 5.57 | 6.00 | 6.30 | 6.45 | 6.56 | 6.74 | 7.19 | 7.82 | 7.64 | 7.56 | 7.44 | 7.24 |
| 6 | ≈ 3.32 | ≈ 5.83 | 6.46 | 6.93 | 7.37 | 7.67 | 7.86 | 8.08 | 8.62 | 9.42 | 9.24 | 9.15 | 9.02 | 8.76 |
| 7 | not rated | ≈ 5.04 | ≈ 7.15 | 7.86 | 8.43 | 8.85 | 9.13 | 9.41 | 10.05 | 10.98 | 10.79 | 10.69 | 10.53 | 10.22 |
| 8 | ≈ 2.12 | ≈ 3.41 | ≈ 7.85 | 8.71 | 9.42 | 9.98 | 10.36 | 10.71 | 11.45 | 12.53 | 12.35 | 12.23 | 12.05 | 11.69 |
| 9 | 2.33 | not rated | ≈ 6.96 | ≈ 9.49 | 10.36 | 11.05 | 11.54 | 11.99 | 12.83 | 14.06 | 13.89 | 13.77 | 13.57 | 13.17 |
| 10 | 2.53 | ≈ 2.49 | ≈ 4.66 | ≈ 10.21 | 11.24 | 12.07 | 12.68 | 13.23 | 14.18 | 15.56 | 15.42 | 15.31 | 15.09 | 14.66 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.424 |
| SC2 | 0 | 8 | 10.713 |
| SC3 | -18 | 7 | 8.105 |
| SC4 | -25 | 6 | 6.456 |
| SC5 | -34 | 6 | 4.306 |
| A | 1957 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1957 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.