EA-DA-x-363BE7-B27 C
31.20 kW
Defrost: Electric
Product code: EA-DA-445AE7-C23 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,943 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 152.1 m² |
| Inner volume | 44.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 226 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 1,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-DA-445AE7-C23 C | None |
|---|---|
| EA-DA-445AE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.27 | 13.53 | 13.75 | 13.92 | 13.99 | 13.97 | 13.88 | 14.05 | 14.92 | 16.14 | 15.75 | 15.61 | 15.41 | 15.10 |
| 5 | 16.45 | 17.05 | 17.58 | 18.02 | 18.24 | 18.25 | 18.20 | 18.36 | 19.48 | 21.09 | 20.53 | 20.32 | 20.02 | 19.56 |
| 6 | 19.38 | 20.26 | 21.14 | 21.91 | 22.38 | 22.61 | 22.66 | 22.88 | 24.27 | 26.29 | 25.59 | 25.32 | 24.91 | 24.24 |
| 7 | 21.82 | 23.17 | 24.40 | 25.49 | 26.24 | 26.71 | 26.96 | 27.31 | 29.03 | 31.54 | 30.83 | 30.50 | 30.00 | 29.15 |
| 8 | ≈ 24.06 | 25.83 | 27.46 | 28.89 | 29.91 | 30.59 | 30.97 | 31.40 | 33.38 | 36.29 | 35.52 | 35.19 | 34.66 | 33.75 |
| 9 | ≈ 26.09 | 28.30 | 30.36 | 32.18 | 33.49 | 34.40 | 34.94 | 35.50 | 37.75 | 41.05 | 40.23 | 39.84 | 39.23 | 38.18 |
| 10 | 27.91 | 30.58 | 33.08 | 35.32 | 36.98 | 38.15 | 38.89 | 39.58 | 42.12 | 45.83 | 44.95 | 44.52 | 43.85 | 42.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 44.954 |
| SC2 | 0 | 8 | 31.403 |
| SC3 | -18 | 7 | 25.824 |
| SC4 | -25 | 6 | 21.144 |
| SC5 | -34 | 6 | 19.624 |
| A | 3467 mm |
|---|---|
| B | 875 mm |
| C | 710 mm |
| F | 710 mm |
| E1 | 768 mm |
| E2 | 750 mm |
| E | 3035 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 3467 mm |
|---|---|
| Width | 875 mm |
| Height | 710 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.