EA-DA-450BE7-C21 C
52.81 kW
Defrost: Electric
Product code: EA-DA-645AE7-C23 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 26,912 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 228.2 m² |
| Inner volume | 67.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 327 kg |
| Quantity | 6 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 2,100 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DA-645AE7-C23 C | None |
|---|---|
| EA-DA-645AE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 21.96 | 21.82 | 21.79 | 21.82 | 21.74 | 21.58 | 21.37 | 21.59 | 22.92 | 24.79 | 24.19 | 23.99 | 23.69 | 23.21 |
| 5 | 27.96 | 28.09 | 28.27 | 28.47 | 28.44 | 28.30 | 28.05 | 28.22 | 29.91 | 32.33 | 31.43 | 31.10 | 30.65 | 29.96 |
| 6 | 33.66 | 34.23 | 34.77 | 35.26 | 35.44 | 35.37 | 35.13 | 35.21 | 37.29 | 40.30 | 39.11 | 38.66 | 38.01 | 36.98 |
| 7 | 39.04 | 39.99 | 41.01 | 41.90 | 42.36 | 42.49 | 42.34 | 42.50 | 45.01 | 48.65 | 47.20 | 46.62 | 45.77 | 44.37 |
| 8 | 43.73 | 45.37 | 46.89 | 48.27 | 49.16 | 49.65 | 49.70 | 49.94 | 52.90 | 57.22 | 55.56 | 54.88 | 53.83 | 52.09 |
| 9 | 48.08 | 50.33 | 52.39 | 54.22 | 55.40 | 56.12 | 56.42 | 56.92 | 60.39 | 65.47 | 63.89 | 63.19 | 62.04 | 59.98 |
| 10 | 52.12 | 55.04 | 57.71 | 60.04 | 61.60 | 62.57 | 63.05 | 63.66 | 67.56 | 73.24 | 71.51 | 70.71 | 69.50 | 67.42 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 71.509 |
| SC2 | 0 | 8 | 49.937 |
| SC3 | -18 | 7 | 42.131 |
| SC4 | -25 | 6 | 34.766 |
| SC5 | -34 | 6 | 33.825 |
| A | 4967 mm |
|---|---|
| B | 875 mm |
| C | 710 mm |
| F | 710 mm |
| E1 | 768 mm |
| E2 | 750 mm |
| E | 4535 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 4967 mm |
|---|---|
| Width | 875 mm |
| Height | 710 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.