EA-DA-135BE7-C21 C
3.59 kW
Defrost: None
Product code: EA-DA-x-135BE7-B21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,040 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 12.7 m² |
| Inner volume | 4.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 48 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø12,7 |
| EA-DA-x-135BE7-B21 C | None |
|---|---|
| EA-DA-x-135BE7-B21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | 1.18 | 1.30 | 1.39 | 1.46 | 1.49 | 1.54 | 1.65 | 1.81 | 1.78 | 1.77 | 1.76 | 1.73 |
| 5 | not rated | not rated | 1.42 | 1.58 | 1.68 | 1.79 | 1.86 | 1.94 | 2.08 | 2.28 | 2.26 | 2.25 | 2.23 | 2.18 |
| 6 | not rated | not rated | not rated | ≈ 1.78 | 1.96 | 2.10 | 2.20 | 2.30 | 2.47 | 2.72 | 2.70 | 2.69 | 2.66 | 2.61 |
| 7 | 0.60 | 0.59 | not rated | ≈ 1.70 | ≈ 2.21 | 2.39 | 2.53 | 2.66 | 2.86 | 3.15 | 3.14 | 3.13 | 3.10 | 3.04 |
| 8 | 0.66 | 0.65 | ≈ 0.65 | ≈ 1.28 | ≈ 2.43 | 2.66 | 2.84 | 3.00 | 3.23 | 3.57 | 3.57 | 3.56 | 3.53 | 3.46 |
| 9 | 0.73 | 0.72 | 0.72 | ≈ 0.73 | ≈ 2.64 | 2.91 | 3.13 | 3.32 | 3.59 | 3.98 | 4.00 | 3.99 | 3.96 | 3.89 |
| 10 | 0.79 | 0.78 | 0.78 | ≈ 0.79 | ≈ 2.19 | ≈ 3.14 | 3.40 | 3.64 | 3.93 | 4.37 | 4.41 | 4.41 | 4.39 | 4.31 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.412 |
| SC2 | 0 | 8 | 2.996 |
| SC3 | -18 | 7 | 2.079 |
| SC4 | -25 | 6 | — |
| SC5 | -34 | 6 | — |
| A | 957 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø12,7 |
| Length | 957 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.