EA-DA-150BE7-C21 C
12.51 kW
Defrost: None
Product code: EA-DA-x-435BE7-B21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,161 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 50.6 m² |
| Inner volume | 18.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 129 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø22 |
| EA-DA-x-435BE7-B21 C | None |
|---|---|
| EA-DA-x-435BE7-B21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 4.58 | 5.03 | 5.42 | 5.71 | 5.89 | 5.95 | 6.11 | 6.52 | 7.11 | 6.97 | 6.92 | 6.84 | 6.74 |
| 5 | not rated | 5.46 | 6.08 | 6.50 | 6.98 | 7.29 | 7.48 | 7.73 | 8.27 | 9.04 | 8.90 | 8.84 | 8.73 | 8.55 |
| 6 | not rated | not rated | 6.59 | ≈ 7.60 | 8.19 | 8.64 | 8.94 | 9.26 | 9.90 | 10.85 | 10.69 | 10.62 | 10.49 | 10.24 |
| 7 | 2.33 | ≈ 2.30 | ≈ 6.57 | ≈ 8.55 | 9.32 | 9.92 | 10.34 | 10.75 | 11.51 | 12.64 | 12.49 | 12.40 | 12.25 | 11.94 |
| 8 | 2.59 | ≈ 2.55 | ≈ 4.69 | ≈ 9.42 | 10.36 | 11.12 | 11.69 | 12.20 | 13.09 | 14.39 | 14.27 | 14.18 | 14.01 | 13.66 |
| 9 | 2.85 | 2.81 | ≈ 2.82 | ≈ 10.21 | 11.32 | 12.25 | 12.97 | 13.61 | 14.62 | 16.11 | 16.03 | 15.94 | 15.76 | 15.38 |
| 10 | 3.11 | 3.06 | ≈ 3.06 | ≈ 8.17 | ≈ 12.21 | 13.32 | 14.19 | 14.97 | 16.11 | 17.78 | 17.76 | 17.68 | 17.51 | 17.11 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.764 |
| SC2 | 0 | 8 | 12.202 |
| SC3 | -18 | 7 | 8.877 |
| SC4 | -25 | 6 | 6.586 |
| SC5 | -34 | 6 | — |
| A | 2457 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø22 |
| Length | 2457 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.