EA-DA-363BE7-C27 C
44.04 kW
Defrost: Electric
Product code: EA-DA-x-463BE7-B27 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 33,818 m³/h |
|---|---|
| Air throw | 27 m |
| External surface | 289.0 m² |
| Inner volume | 83.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 414 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 2,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 79.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-DA-x-463BE7-B27 C | None |
|---|---|
| EA-DA-x-463BE7-B27 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 16.14 | 17.56 | 18.57 | 19.46 | 20.06 | 20.39 | 20.96 | 22.37 | 24.36 | 23.96 | 23.80 | 23.54 | 23.10 |
| 5 | not rated | not rated | 21.14 | 23.00 | 24.43 | 25.49 | 26.21 | 27.03 | 28.90 | 31.61 | 31.25 | 31.09 | 30.84 | 30.33 |
| 6 | ≈ 7.32 | ≈ 18.35 | 24.34 | 26.75 | 28.73 | 30.25 | 31.34 | 32.41 | 34.69 | 38.01 | 37.65 | 37.47 | 37.16 | 36.59 |
| 7 | ≈ 8.30 | ≈ 12.81 | ≈ 27.17 | 30.21 | 32.77 | 34.81 | 36.33 | 37.71 | 40.41 | 44.39 | 44.07 | 43.88 | 43.53 | 42.84 |
| 8 | 9.27 | ≈ 9.10 | ≈ 26.65 | ≈ 33.37 | 36.54 | 39.14 | 41.14 | 42.89 | 46.03 | 50.68 | 50.45 | 50.26 | 49.90 | 49.13 |
| 9 | 10.22 | ≈ 10.04 | ≈ 15.56 | ≈ 36.25 | 40.04 | 43.24 | 45.76 | 47.93 | 51.52 | 56.83 | 56.76 | 56.60 | 56.25 | 55.43 |
| 10 | 11.14 | 10.97 | ≈ 10.98 | ≈ 38.92 | 43.28 | 47.07 | 50.16 | 52.80 | 56.85 | 62.85 | 62.98 | 62.86 | 62.55 | 61.72 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 14.71 | 15.77 | 16.68 | 17.30 | 17.67 | 17.68 | 18.08 | 19.28 | 20.98 | 20.60 | 20.45 | 20.23 | 19.88 |
| 5 | not rated | not rated | 19.20 | 20.63 | 21.71 | 22.45 | 22.83 | 23.47 | 24.97 | 27.22 | 26.73 | 26.52 | 26.29 | 25.77 |
| 6 | not rated | ≈ 19.64 | 22.35 | 24.30 | 25.83 | 26.94 | 27.57 | 28.51 | 30.46 | 33.30 | 32.83 | 32.61 | 32.25 | 31.52 |
| 7 | ≈ 7.01 | ≈ 19.22 | ≈ 25.08 | 27.53 | 29.58 | 31.10 | 32.03 | 33.19 | 35.48 | 38.86 | 38.20 | 37.95 | 37.52 | 36.72 |
| 8 | ≈ 7.81 | ≈ 13.17 | ≈ 27.57 | 30.56 | 33.12 | 35.10 | 36.48 | 37.79 | 40.44 | 44.35 | 43.70 | 43.41 | 42.92 | 41.96 |
| 9 | ≈ 8.59 | ≈ 14.53 | ≈ 29.86 | 33.35 | 36.45 | 38.89 | 40.56 | 42.30 | 45.32 | 49.61 | 49.17 | 48.87 | 48.33 | 47.23 |
| 10 | 9.36 | ≈ 9.21 | ≈ 18.88 | ≈ 35.91 | 39.54 | 42.51 | 44.60 | 46.71 | 49.96 | 54.93 | 54.61 | 54.30 | 53.73 | 52.55 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 62.983 | 54.607 |
| SC2 | 0 | 8 | 42.891 | 37.789 |
| SC3 | -18 | 7 | 31.287 | 28.430 |
| SC4 | -25 | 6 | 24.337 | 22.346 |
| SC5 | -34 | 6 | — | — |
| A | 4207 mm |
|---|---|
| B | 1000 mm |
| C | 1010 mm |
| F | 710 mm |
| E1 | 968 mm |
| E2 | 950 mm |
| E | 3835 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 4207 mm |
|---|---|
| Width | 1000 mm |
| Height | 1010 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.