EA-DA-x-250BE7-B22 C
18.59 kW
Defrost: Electric
Product code: EA-DA-x-635BE7-B21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,242 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 75.9 m² |
| Inner volume | 28.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 182 kg |
| Quantity | 6 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 990 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-DA-x-635BE7-B21 C | None |
|---|---|
| EA-DA-x-635BE7-B21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 6.95 | 7.62 | 8.20 | 8.62 | 8.87 | 8.95 | 9.18 | 9.81 | 10.69 | 10.48 | 10.40 | 10.28 | 10.11 |
| 5 | not rated | 8.30 | 9.22 | 9.84 | 10.54 | 10.99 | 11.27 | 11.64 | 12.44 | 13.60 | 13.37 | 13.28 | 13.12 | 12.84 |
| 6 | not rated | not rated | 10.06 | 11.51 | 12.38 | 13.03 | 13.47 | 13.94 | 14.90 | 16.32 | 16.08 | 15.96 | 15.76 | 15.38 |
| 7 | 3.50 | not rated | ≈ 10.37 | ≈ 12.97 | 14.10 | 14.98 | 15.60 | 16.19 | 17.33 | 19.02 | 18.78 | 18.65 | 18.40 | 17.94 |
| 8 | 3.89 | ≈ 3.83 | ≈ 7.72 | ≈ 14.30 | 15.69 | 16.81 | 17.64 | 18.39 | 19.72 | 21.66 | 21.47 | 21.32 | 21.06 | 20.52 |
| 9 | 4.28 | 4.21 | ≈ 4.24 | ≈ 15.51 | 17.16 | 18.54 | 19.59 | 20.53 | 22.04 | 24.26 | 24.13 | 23.98 | 23.70 | 23.11 |
| 10 | 4.66 | 4.59 | ≈ 4.60 | ≈ 14.10 | ≈ 18.52 | 20.16 | 21.45 | 22.59 | 24.29 | 26.80 | 26.74 | 26.61 | 26.33 | 25.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.743 |
| SC2 | 0 | 8 | 18.392 |
| SC3 | -18 | 7 | 13.447 |
| SC4 | -25 | 6 | 10.058 |
| SC5 | -34 | 6 | — |
| A | 3457 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 3035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 3457 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.