EA-DI-263GE10-A13 C
47.68 kW
Defrost: None
Product code: EA-DI-263GC4-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 36,778 m³/h |
|---|---|
| External surface | 216.9 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 377 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DI-263GC4-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.24 | 20.21 | 20.21 | 20.20 | 20.11 | 19.96 | 19.77 | 19.79 | 20.93 | 22.58 | 21.97 | 21.75 | 21.44 | 20.96 |
| 5 | 25.89 | 26.33 | 26.69 | 26.88 | 26.91 | 26.80 | 26.58 | 26.56 | 28.09 | 30.30 | 29.44 | 29.13 | 28.68 | 28.00 |
| 6 | 30.94 | 31.90 | 32.79 | 33.59 | 34.08 | 34.14 | 34.00 | 34.01 | 35.99 | 38.83 | 37.70 | 37.27 | 36.66 | 35.71 |
| 7 | 35.30 | 36.83 | 38.19 | 39.39 | 40.15 | 40.59 | 40.81 | 41.10 | 43.61 | 47.28 | 46.23 | 45.82 | 45.22 | 44.09 |
| 8 | 39.35 | 41.51 | 43.44 | 45.10 | 46.21 | 46.90 | 47.27 | 47.65 | 50.58 | 54.86 | 53.65 | 53.17 | 52.46 | 51.29 |
| 9 | 43.07 | 45.91 | 48.47 | 50.70 | 52.23 | 53.21 | 53.78 | 54.28 | 57.65 | 62.57 | 61.23 | 60.68 | 59.86 | 58.51 |
| 10 | 46.44 | 50.03 | 53.30 | 56.13 | 58.14 | 59.49 | 60.30 | 60.97 | 64.79 | 70.37 | 68.92 | 68.32 | 67.40 | 65.86 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.91 | 17.78 | 17.69 | 17.70 | 17.63 | 17.52 | 17.39 | 17.45 | 18.50 | 19.99 | 19.50 | 19.32 | 19.06 | 18.68 |
| 5 | 22.92 | 23.07 | 23.23 | 23.38 | 23.37 | 23.23 | 23.05 | 23.07 | 24.43 | 26.38 | 25.68 | 25.42 | 25.06 | 24.50 |
| 6 | 27.76 | 28.35 | 28.74 | 29.18 | 29.35 | 29.33 | 29.18 | 29.19 | 30.89 | 33.35 | 32.40 | 32.05 | 31.55 | 30.77 |
| 7 | 31.93 | 32.96 | 33.92 | 34.78 | 35.33 | 35.64 | 35.62 | 35.67 | 37.77 | 40.80 | 39.65 | 39.20 | 38.56 | 37.54 |
| 8 | 35.73 | 37.25 | 38.63 | 39.86 | 40.65 | 41.12 | 41.36 | 41.65 | 44.20 | 47.93 | 46.86 | 46.44 | 45.80 | 44.68 |
| 9 | 39.26 | 41.35 | 43.22 | 44.85 | 45.95 | 46.63 | 47.00 | 47.37 | 50.28 | 54.55 | 53.34 | 52.84 | 52.10 | 50.87 |
| 10 | 42.52 | 45.20 | 47.63 | 49.73 | 51.19 | 52.11 | 52.66 | 53.15 | 56.43 | 61.24 | 59.92 | 59.36 | 58.51 | 57.09 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 68.923 | 59.918 |
| SC2 | 0 | 8 | 47.645 | 41.649 |
| SC3 | -18 | 7 | 39.735 | 35.033 |
| SC4 | -25 | 6 | 32.790 | 28.743 |
| SC5 | -34 | 6 | 31.184 | 27.928 |
| A | 3025 mm |
|---|---|
| B | 900 mm |
| C | 1150 mm |
| F | 860 mm |
| G | 1440 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3025 mm |
|---|---|
| Width | 1440 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.