EA-DI-263GE10-A13 C
47.68 kW
Defrost: None
Product code: EA-DI-363GC10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 51,522 m³/h |
|---|---|
| External surface | 158.7 m² |
| Inner volume | 66.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 533 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 5,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-363GC10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.57 | 20.03 | 19.66 | 19.42 | 19.14 | 18.85 | 18.56 | 18.44 | 19.45 | 20.92 | 20.28 | 20.04 | 19.71 | 19.21 |
| 5 | 27.04 | 26.57 | 26.32 | 26.15 | 25.87 | 25.53 | 25.15 | 24.96 | 26.34 | 28.33 | 27.41 | 27.07 | 26.59 | 25.85 |
| 6 | 33.41 | 33.30 | 33.28 | 33.31 | 33.09 | 32.78 | 32.38 | 32.14 | 33.93 | 36.49 | 35.27 | 34.81 | 34.16 | 33.17 |
| 7 | 39.56 | 39.91 | 40.26 | 40.60 | 40.61 | 40.41 | 40.05 | 39.76 | 42.00 | 45.21 | 43.73 | 43.17 | 42.35 | 41.07 |
| 8 | 45.40 | 46.14 | 46.99 | 47.74 | 48.07 | 48.08 | 47.87 | 47.71 | 50.44 | 54.37 | 52.67 | 52.00 | 51.03 | 49.49 |
| 9 | 50.34 | 51.77 | 53.13 | 54.42 | 55.24 | 55.72 | 55.84 | 55.81 | 59.06 | 63.78 | 61.92 | 61.17 | 60.08 | 58.29 |
| 10 | 55.06 | 57.09 | 58.97 | 60.69 | 61.81 | 62.52 | 62.90 | 63.25 | 67.10 | 72.73 | 71.09 | 70.42 | 69.31 | 67.31 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.34 | 17.82 | 17.50 | 17.31 | 17.09 | 16.87 | 16.66 | 16.58 | 17.51 | 18.86 | 18.32 | 18.12 | 17.84 | 17.42 |
| 5 | 23.96 | 23.51 | 23.24 | 23.09 | 22.86 | 22.59 | 22.28 | 22.15 | 23.39 | 25.19 | 24.42 | 24.14 | 23.74 | 23.13 |
| 6 | 29.69 | 29.41 | 29.28 | 29.21 | 29.04 | 28.78 | 28.43 | 28.26 | 29.84 | 32.12 | 31.11 | 30.73 | 30.19 | 29.36 |
| 7 | 35.24 | 35.26 | 35.38 | 35.55 | 35.50 | 35.27 | 34.93 | 34.77 | 36.73 | 39.56 | 38.30 | 37.83 | 37.10 | 36.03 |
| 8 | 40.57 | 41.00 | 41.46 | 41.92 | 42.06 | 41.92 | 41.65 | 41.52 | 43.88 | 47.31 | 45.81 | 45.25 | 44.42 | 43.08 |
| 9 | 45.64 | 46.41 | 47.30 | 48.12 | 48.54 | 48.66 | 48.50 | 48.40 | 51.20 | 55.26 | 53.67 | 53.01 | 52.03 | 50.46 |
| 10 | 49.99 | 51.36 | 52.71 | 53.98 | 54.83 | 55.35 | 55.41 | 55.42 | 58.68 | 63.41 | 61.67 | 60.94 | 59.86 | 58.08 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 71.089 | 61.669 |
| SC2 | 0 | 8 | 47.714 | 41.523 |
| SC3 | -18 | 7 | 40.636 | 35.550 |
| SC4 | -25 | 6 | 33.284 | 29.277 |
| SC5 | -34 | 6 | 33.434 | 29.669 |
| A | 4325 mm |
|---|---|
| B | 900 mm |
| C | 1150 mm |
| F | 860 mm |
| G | 1440 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 4325 mm |
|---|---|
| Width | 1440 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.