EA-DR-245EA10-A07 C
7.60 kW
Defrost: None
Product code: EA-DR-245BB10-A07 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,760 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 31.9 m² |
| Inner volume | 12.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 107 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,360 rpm |
| Power | 960 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.4 dB(A) |
| Energy class | E |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-DR-245BB10-A07 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | 3.75 | 3.81 | 3.83 | 3.82 | 3.82 | 4.05 | 4.37 | 4.24 | 4.19 | 4.12 | 4.01 |
| 5 | 4.04 | 4.29 | 4.57 | 4.79 | 4.94 | 5.04 | 5.08 | 5.13 | 5.45 | 5.90 | 5.76 | 5.70 | 5.61 | 5.47 |
| 6 | ≈ 4.64 | 5.03 | 5.40 | 5.73 | 5.97 | 6.14 | 6.25 | 6.36 | 6.77 | 7.37 | 7.24 | 7.19 | 7.11 | 6.98 |
| 7 | ≈ 5.15 | 5.67 | 6.15 | 6.59 | 6.92 | 7.17 | 7.34 | 7.49 | 7.98 | 8.70 | 8.58 | 8.52 | 8.43 | 8.28 |
| 8 | ≈ 3.80 | ≈ 6.24 | 6.85 | 7.41 | 7.84 | 8.18 | 8.42 | 8.61 | 9.19 | 10.04 | 9.91 | 9.85 | 9.76 | 9.59 |
| 9 | ≈ 2.11 | ≈ 6.76 | 7.49 | 8.18 | 8.73 | 9.15 | 9.47 | 9.72 | 10.39 | 11.37 | 11.25 | 11.19 | 11.10 | 10.92 |
| 10 | ≈ 2.30 | ≈ 6.67 | ≈ 8.08 | 8.89 | 9.56 | 10.10 | 10.50 | 10.82 | 11.57 | 12.68 | 12.58 | 12.53 | 12.43 | 12.25 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | 3.38 | 3.42 | 3.43 | 3.42 | 3.43 | 3.64 | 3.93 | 3.82 | 3.77 | 3.71 | 3.61 |
| 5 | 3.77 | 4.00 | 4.17 | 4.34 | 4.45 | 4.51 | 4.53 | 4.57 | 4.85 | 5.25 | 5.11 | 5.06 | 4.99 | 4.87 |
| 6 | 4.39 | 4.69 | 4.99 | 5.26 | 5.45 | 5.58 | 5.66 | 5.74 | 6.10 | 6.62 | 6.48 | 6.42 | 6.33 | 6.18 |
| 7 | ≈ 4.88 | 5.31 | 5.71 | 6.07 | 6.33 | 6.52 | 6.65 | 6.77 | 7.21 | 7.85 | 7.72 | 7.67 | 7.58 | 7.43 |
| 8 | ≈ 5.33 | 5.87 | 6.38 | 6.84 | 7.19 | 7.45 | 7.63 | 7.78 | 8.30 | 9.05 | 8.92 | 8.86 | 8.76 | 8.60 |
| 9 | ≈ 3.84 | ≈ 6.38 | 7.00 | 7.57 | 8.02 | 8.35 | 8.60 | 8.79 | 9.38 | 10.25 | 10.12 | 10.06 | 9.96 | 9.77 |
| 10 | ≈ 2.05 | ≈ 6.84 | 7.58 | 8.26 | 8.81 | 9.23 | 9.54 | 9.79 | 10.46 | 11.44 | 11.32 | 11.25 | 11.15 | 10.95 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 12.583 | 11.316 |
| SC2 | 0 | 8 | 8.611 | 7.784 |
| SC3 | -18 | 7 | 6.734 | 6.182 |
| SC4 | -25 | 6 | 5.399 | 4.992 |
| SC5 | -34 | 6 | 4.724 | 4.469 |
| A | 1867 mm |
|---|---|
| B | 700 mm |
| C | 775 mm |
| F | 660 mm |
| E1 | 768 mm |
| E | 1535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1867 mm |
|---|---|
| Width | 700 mm |
| Height | 775 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.