EA-DV-180GC4-A01 C
29.00 kW
Defrost: None
Product code: EA-DV-163GG10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,708 m³/h |
|---|---|
| External surface | 105.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 284 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GG10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.71 | 12.46 | 12.30 | 12.21 | 12.09 | 11.93 | 11.77 | 11.81 | 12.51 | 13.49 | 13.12 | 12.99 | 12.79 | 12.48 |
| 5 | 16.38 | 16.22 | 16.15 | 16.12 | 16.00 | 15.83 | 15.62 | 15.63 | 16.53 | 17.82 | 17.27 | 17.07 | 16.79 | 16.37 |
| 6 | 20.07 | 20.07 | 20.13 | 20.20 | 20.12 | 19.97 | 19.74 | 19.71 | 20.83 | 22.45 | 21.72 | 21.44 | 21.05 | 20.44 |
| 7 | 23.56 | 23.82 | 24.08 | 24.33 | 24.37 | 24.27 | 24.03 | 23.99 | 25.36 | 27.34 | 26.43 | 26.08 | 25.57 | 24.76 |
| 8 | 26.88 | 27.45 | 27.98 | 28.36 | 28.57 | 28.57 | 28.41 | 28.38 | 30.01 | 32.37 | 31.31 | 30.89 | 30.28 | 29.30 |
| 9 | 30.00 | 30.81 | 31.66 | 32.40 | 32.78 | 32.91 | 32.83 | 32.86 | 34.76 | 37.51 | 36.36 | 35.88 | 35.18 | 34.03 |
| 10 | 32.64 | 33.89 | 35.04 | 36.08 | 36.72 | 37.09 | 37.23 | 37.37 | 39.56 | 42.72 | 41.48 | 40.95 | 40.17 | 38.86 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.97 | 10.72 | 10.59 | 10.52 | 10.43 | 10.31 | 10.19 | 10.27 | 10.89 | 11.77 | 11.47 | 11.37 | 11.22 | 11.00 |
| 5 | 14.09 | 13.89 | 13.79 | 13.75 | 13.66 | 13.52 | 13.35 | 13.39 | 14.18 | 15.31 | 14.86 | 14.70 | 14.47 | 14.14 |
| 6 | 17.26 | 17.10 | 17.09 | 17.12 | 17.05 | 16.91 | 16.71 | 16.72 | 17.68 | 19.08 | 18.47 | 18.24 | 17.92 | 17.41 |
| 7 | 20.32 | 20.35 | 20.45 | 20.57 | 20.55 | 20.43 | 20.22 | 20.20 | 21.36 | 23.04 | 22.27 | 21.98 | 21.55 | 20.86 |
| 8 | 23.26 | 23.50 | 23.77 | 24.04 | 24.11 | 24.04 | 23.82 | 23.80 | 25.16 | 27.13 | 26.23 | 25.87 | 25.34 | 24.47 |
| 9 | 26.07 | 26.56 | 27.04 | 27.48 | 27.66 | 27.62 | 27.46 | 27.46 | 29.03 | 31.29 | 30.29 | 29.87 | 29.25 | 28.22 |
| 10 | 28.72 | 29.51 | 30.15 | 30.80 | 31.13 | 31.24 | 31.14 | 31.17 | 32.96 | 35.56 | 34.46 | 33.98 | 33.26 | 32.08 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 41.477 | 34.455 |
| SC2 | 0 | 8 | 28.382 | 23.800 |
| SC3 | -18 | 7 | 24.367 | 20.563 |
| SC4 | -25 | 6 | 20.125 | 17.086 |
| SC5 | -34 | 6 | 20.095 | 17.256 |
| A | 1725 mm |
|---|---|
| B | 1100 mm |
| C | 1260 mm |
| F | 1060 mm |
| G | 1785 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1785 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.