EA-DV-163GI7-A13 C
37.88 kW
Defrost: None
Product code: EA-DV-163GG4-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,640 m³/h |
|---|---|
| External surface | 216.9 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 302 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GG4-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.59 | 17.53 | 17.60 | 17.70 | 17.70 | 17.62 | 17.50 | 17.67 | 18.75 | 20.30 | 19.83 | 19.67 | 19.44 | 19.09 |
| 5 | 22.09 | 22.37 | 22.65 | 22.91 | 22.99 | 22.91 | 22.76 | 22.88 | 24.26 | 26.23 | 25.53 | 25.27 | 24.91 | 24.35 |
| 6 | 26.38 | 27.07 | 27.68 | 28.10 | 28.36 | 28.40 | 28.27 | 28.38 | 30.06 | 32.50 | 31.56 | 31.20 | 30.68 | 29.85 |
| 7 | 30.21 | 31.32 | 32.35 | 33.27 | 33.82 | 34.01 | 33.97 | 34.10 | 36.11 | 39.06 | 37.92 | 37.47 | 36.80 | 35.71 |
| 8 | 33.64 | 35.22 | 36.65 | 37.92 | 38.73 | 39.20 | 39.38 | 39.69 | 42.11 | 45.64 | 44.47 | 43.93 | 43.13 | 41.76 |
| 9 | 36.82 | 38.91 | 40.81 | 42.46 | 43.57 | 44.22 | 44.53 | 44.91 | 47.65 | 51.64 | 50.41 | 49.88 | 49.06 | 47.63 |
| 10 | 39.73 | 42.38 | 44.79 | 46.89 | 48.33 | 49.22 | 49.69 | 50.16 | 53.23 | 57.70 | 56.36 | 55.75 | 54.81 | 53.17 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.56 | 14.48 | 14.49 | 14.55 | 14.54 | 14.48 | 14.37 | 14.60 | 15.53 | 16.84 | 16.47 | 16.35 | 16.18 | 15.93 |
| 5 | 18.34 | 18.38 | 18.45 | 18.60 | 18.63 | 18.56 | 18.41 | 18.59 | 19.72 | 21.36 | 20.79 | 20.58 | 20.28 | 19.83 |
| 6 | 21.96 | 22.23 | 22.52 | 22.80 | 22.89 | 22.82 | 22.65 | 22.78 | 24.13 | 26.11 | 25.33 | 25.03 | 24.59 | 23.89 |
| 7 | 25.43 | 26.00 | 26.53 | 27.00 | 27.16 | 27.17 | 27.01 | 27.11 | 28.69 | 31.01 | 30.04 | 29.65 | 29.08 | 28.13 |
| 8 | 28.69 | 29.50 | 30.34 | 31.07 | 31.46 | 31.56 | 31.44 | 31.55 | 33.39 | 36.06 | 34.95 | 34.47 | 33.76 | 32.62 |
| 9 | 31.53 | 32.80 | 33.96 | 34.99 | 35.64 | 35.95 | 35.92 | 36.07 | 38.17 | 41.21 | 39.95 | 39.40 | 38.56 | 37.25 |
| 10 | 34.21 | 35.87 | 37.39 | 38.72 | 39.55 | 40.01 | 40.13 | 40.41 | 42.81 | 46.30 | 45.03 | 44.40 | 43.44 | 41.97 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 56.356 | 45.029 |
| SC2 | 0 | 8 | 39.693 | 31.553 |
| SC3 | -18 | 7 | 33.535 | 27.116 |
| SC4 | -25 | 6 | 27.682 | 22.516 |
| SC5 | -34 | 6 | 26.564 | 22.051 |
| A | 1725 mm |
|---|---|
| B | 1100 mm |
| C | 1260 mm |
| F | 1060 mm |
| G | 1785 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1785 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.