EA-DV-163GI7-A13 C
37.88 kW
Defrost: None
Product code: EA-DV-263GC7-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 37,606 m³/h |
|---|---|
| External surface | 146.2 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 428 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-263GC7-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.70 | 15.43 | 15.25 | 15.13 | 14.97 | 14.79 | 14.61 | 14.54 | 15.36 | 16.54 | 16.07 | 15.89 | 15.65 | 15.29 |
| 5 | 20.53 | 20.43 | 20.38 | 20.36 | 20.20 | 19.99 | 19.74 | 19.64 | 20.75 | 22.34 | 21.66 | 21.41 | 21.05 | 20.50 |
| 6 | 25.20 | 25.45 | 25.67 | 25.87 | 25.85 | 25.69 | 25.43 | 25.29 | 26.70 | 28.74 | 27.84 | 27.51 | 27.03 | 26.29 |
| 7 | 29.63 | 30.20 | 30.83 | 31.35 | 31.56 | 31.56 | 31.38 | 31.30 | 33.09 | 35.66 | 34.57 | 34.15 | 33.53 | 32.56 |
| 8 | 33.27 | 34.37 | 35.39 | 36.32 | 36.91 | 37.26 | 37.41 | 37.54 | 39.73 | 42.89 | 41.65 | 41.16 | 40.45 | 39.30 |
| 9 | 36.75 | 38.33 | 39.76 | 41.03 | 41.87 | 42.39 | 42.66 | 42.93 | 45.56 | 49.39 | 48.30 | 47.86 | 47.21 | 46.14 |
| 10 | 39.99 | 42.10 | 44.00 | 45.66 | 46.80 | 47.53 | 47.95 | 48.32 | 51.29 | 55.65 | 54.46 | 53.97 | 53.24 | 52.04 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.96 | 13.67 | 13.50 | 13.41 | 13.29 | 13.16 | 13.03 | 13.03 | 13.77 | 14.86 | 14.48 | 14.34 | 14.14 | 13.84 |
| 5 | 18.19 | 18.00 | 17.86 | 17.83 | 17.71 | 17.55 | 17.37 | 17.32 | 18.31 | 19.75 | 19.20 | 19.00 | 18.71 | 18.29 |
| 6 | 22.36 | 22.39 | 22.45 | 22.54 | 22.49 | 22.32 | 22.12 | 22.04 | 23.30 | 25.11 | 24.36 | 24.09 | 23.69 | 23.08 |
| 7 | 26.38 | 26.73 | 27.07 | 27.37 | 27.39 | 27.32 | 27.15 | 27.07 | 28.61 | 30.85 | 29.93 | 29.58 | 29.07 | 28.28 |
| 8 | 30.18 | 30.80 | 31.50 | 32.09 | 32.39 | 32.46 | 32.36 | 32.33 | 34.20 | 36.91 | 35.83 | 35.41 | 34.79 | 33.81 |
| 9 | 33.34 | 34.43 | 35.45 | 36.39 | 37.00 | 37.36 | 37.55 | 37.71 | 39.93 | 43.15 | 41.95 | 41.48 | 40.77 | 39.63 |
| 10 | 36.40 | 37.91 | 39.29 | 40.53 | 41.35 | 41.88 | 42.17 | 42.44 | 45.04 | 48.84 | 47.77 | 47.34 | 46.69 | 45.62 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 54.456 | 47.771 |
| SC2 | 0 | 8 | 37.539 | 32.326 |
| SC3 | -18 | 7 | 31.464 | 27.422 |
| SC4 | -25 | 6 | 25.674 | 22.454 |
| SC5 | -34 | 6 | 25.290 | 22.396 |
| A | 3025 mm |
|---|---|
| B | 900 mm |
| C | 1260 mm |
| F | 860 mm |
| G | 1585 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3025 mm |
|---|---|
| Width | 1585 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.