EA-DV-263GC7-A08 C
36.31 kW
Defrost: None
Product code: EA-DV-163GI10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,157 m³/h |
|---|---|
| External surface | 132.0 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 320 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GI10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.42 | 15.27 | 15.20 | 15.17 | 15.06 | 14.91 | 14.72 | 14.76 | 15.63 | 16.86 | 16.38 | 16.21 | 15.97 | 15.59 |
| 5 | 19.70 | 19.74 | 19.77 | 19.88 | 19.84 | 19.70 | 19.49 | 19.49 | 20.62 | 22.23 | 21.55 | 21.29 | 20.94 | 20.39 |
| 6 | 23.74 | 24.09 | 24.43 | 24.73 | 24.81 | 24.71 | 24.51 | 24.50 | 25.91 | 27.95 | 27.06 | 26.72 | 26.23 | 25.45 |
| 7 | 27.56 | 28.30 | 28.97 | 29.54 | 29.72 | 29.78 | 29.65 | 29.67 | 31.38 | 33.87 | 32.81 | 32.39 | 31.77 | 30.76 |
| 8 | 31.12 | 32.16 | 33.21 | 34.13 | 34.66 | 34.87 | 34.85 | 34.93 | 36.98 | 39.95 | 38.76 | 38.27 | 37.54 | 36.33 |
| 9 | 34.15 | 35.73 | 37.17 | 38.46 | 39.28 | 39.79 | 40.02 | 40.24 | 42.62 | 46.08 | 44.80 | 44.25 | 43.42 | 42.03 |
| 10 | 37.02 | 39.07 | 40.94 | 42.58 | 43.68 | 44.37 | 44.73 | 45.11 | 47.86 | 51.87 | 50.66 | 50.13 | 49.32 | 47.79 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.97 | 12.78 | 12.69 | 12.66 | 12.57 | 12.45 | 12.30 | 12.42 | 13.18 | 14.25 | 13.89 | 13.76 | 13.58 | 13.31 |
| 5 | 16.49 | 16.41 | 16.41 | 16.44 | 16.38 | 16.25 | 16.05 | 16.14 | 17.09 | 18.46 | 17.90 | 17.70 | 17.42 | 16.99 |
| 6 | 20.01 | 20.08 | 20.21 | 20.33 | 20.33 | 20.22 | 20.01 | 20.05 | 21.21 | 22.90 | 22.16 | 21.88 | 21.47 | 20.82 |
| 7 | 23.34 | 23.65 | 23.97 | 24.28 | 24.38 | 24.29 | 24.09 | 24.11 | 25.50 | 27.52 | 26.60 | 26.24 | 25.71 | 24.84 |
| 8 | 26.50 | 27.11 | 27.68 | 28.19 | 28.43 | 28.42 | 28.25 | 28.24 | 29.86 | 32.22 | 31.18 | 30.74 | 30.09 | 29.02 |
| 9 | 29.46 | 30.43 | 31.19 | 31.95 | 32.35 | 32.48 | 32.38 | 32.46 | 34.33 | 37.04 | 35.87 | 35.37 | 34.61 | 33.35 |
| 10 | 32.24 | 33.43 | 34.62 | 35.69 | 36.30 | 36.58 | 36.56 | 36.69 | 38.82 | 41.90 | 40.64 | 40.07 | 39.22 | 37.76 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 50.662 | 40.638 |
| SC2 | 0 | 8 | 34.932 | 28.239 |
| SC3 | -18 | 7 | 29.585 | 24.342 |
| SC4 | -25 | 6 | 24.426 | 20.212 |
| SC5 | -34 | 6 | 23.849 | 20.053 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1260 mm |
| F | 1160 mm |
| G | 1885 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1885 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.