EA-DV-163GE4-A13 C
33.28 kW
Defrost: None
Product code: EA-DV-263GC10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 38,116 m³/h |
|---|---|
| External surface | 105.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 426 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-263GC10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.07 | 13.72 | 13.47 | 13.29 | 13.08 | 12.86 | 12.65 | 12.53 | 13.21 | 14.19 | 13.73 | 13.56 | 13.33 | 12.98 |
| 5 | 18.54 | 18.30 | 18.11 | 18.01 | 17.81 | 17.56 | 17.28 | 17.11 | 18.04 | 19.38 | 18.72 | 18.48 | 18.13 | 17.60 |
| 6 | 22.89 | 22.92 | 22.97 | 23.02 | 22.90 | 22.66 | 22.38 | 22.18 | 23.40 | 25.14 | 24.27 | 23.95 | 23.48 | 22.77 |
| 7 | 27.06 | 27.45 | 27.80 | 28.02 | 28.08 | 27.98 | 27.75 | 27.57 | 29.12 | 31.32 | 30.28 | 29.88 | 29.30 | 28.39 |
| 8 | 30.80 | 31.56 | 32.31 | 33.01 | 33.33 | 33.40 | 33.28 | 33.17 | 35.07 | 37.80 | 36.62 | 36.15 | 35.47 | 34.38 |
| 9 | 34.13 | 35.30 | 36.38 | 37.36 | 38.00 | 38.38 | 38.57 | 38.75 | 41.09 | 44.44 | 43.17 | 42.66 | 41.90 | 40.67 |
| 10 | 37.26 | 38.87 | 40.33 | 41.65 | 42.52 | 43.07 | 43.39 | 43.64 | 46.31 | 50.20 | 49.09 | 48.63 | 47.96 | 46.82 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.44 | 12.10 | 11.88 | 11.74 | 11.58 | 11.42 | 11.25 | 11.22 | 11.84 | 12.75 | 12.38 | 12.24 | 12.05 | 11.76 |
| 5 | 16.29 | 16.02 | 15.85 | 15.74 | 15.57 | 15.37 | 15.15 | 15.07 | 15.92 | 17.13 | 16.60 | 16.40 | 16.13 | 15.71 |
| 6 | 20.20 | 20.07 | 20.02 | 19.98 | 19.86 | 19.66 | 19.42 | 19.30 | 20.39 | 21.93 | 21.21 | 20.95 | 20.57 | 19.99 |
| 7 | 23.95 | 24.07 | 24.21 | 24.36 | 24.34 | 24.19 | 23.95 | 23.82 | 25.16 | 27.09 | 26.20 | 25.86 | 25.37 | 24.61 |
| 8 | 27.54 | 27.97 | 28.38 | 28.68 | 28.81 | 28.77 | 28.61 | 28.51 | 30.13 | 32.47 | 31.44 | 31.05 | 30.47 | 29.55 |
| 9 | 30.75 | 31.53 | 32.28 | 32.99 | 33.33 | 33.43 | 33.36 | 33.32 | 35.24 | 38.04 | 36.91 | 36.47 | 35.81 | 34.74 |
| 10 | 33.70 | 34.81 | 35.85 | 36.80 | 37.43 | 37.80 | 37.99 | 38.18 | 40.43 | 43.70 | 42.50 | 42.01 | 41.28 | 40.09 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 49.087 | 42.496 |
| SC2 | 0 | 8 | 33.174 | 28.506 |
| SC3 | -18 | 7 | 28.068 | 24.371 |
| SC4 | -25 | 6 | 22.965 | 20.015 |
| SC5 | -34 | 6 | 22.932 | 20.197 |
| A | 3025 mm |
|---|---|
| B | 900 mm |
| C | 1260 mm |
| F | 860 mm |
| G | 1585 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3025 mm |
|---|---|
| Width | 1585 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.