EA-DV-191GE10-A04 C
32.21 kW
Defrost: None
Product code: EA-DV-263GC10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 34,345 m³/h |
|---|---|
| External surface | 105.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 421 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-263GC10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.73 | 13.39 | 13.16 | 13.00 | 12.81 | 12.61 | 12.41 | 12.33 | 13.00 | 13.98 | 13.54 | 13.38 | 13.15 | 12.82 |
| 5 | 18.05 | 17.81 | 17.62 | 17.53 | 17.35 | 17.12 | 16.86 | 16.73 | 17.65 | 18.98 | 18.35 | 18.12 | 17.80 | 17.29 |
| 6 | 22.26 | 22.25 | 22.28 | 22.33 | 22.22 | 22.00 | 21.73 | 21.57 | 22.77 | 24.48 | 23.66 | 23.35 | 22.91 | 22.24 |
| 7 | 26.31 | 26.63 | 26.93 | 27.20 | 27.18 | 27.08 | 26.86 | 26.71 | 28.21 | 30.37 | 29.37 | 28.99 | 28.44 | 27.57 |
| 8 | 30.12 | 30.72 | 31.38 | 31.95 | 32.22 | 32.26 | 32.14 | 32.05 | 33.88 | 36.53 | 35.40 | 34.95 | 34.30 | 33.26 |
| 9 | 33.30 | 34.36 | 35.36 | 36.27 | 36.86 | 37.22 | 37.39 | 37.49 | 39.67 | 42.85 | 41.62 | 41.12 | 40.39 | 39.19 |
| 10 | 36.37 | 37.85 | 39.20 | 40.43 | 41.24 | 41.75 | 42.03 | 42.28 | 44.86 | 48.63 | 47.54 | 47.09 | 46.43 | 45.26 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.25 | 11.92 | 11.71 | 11.58 | 11.43 | 11.28 | 11.14 | 11.08 | 11.69 | 12.60 | 12.23 | 12.09 | 11.90 | 11.62 |
| 5 | 15.99 | 15.72 | 15.56 | 15.47 | 15.32 | 15.13 | 14.92 | 14.83 | 15.66 | 16.86 | 16.34 | 16.15 | 15.87 | 15.46 |
| 6 | 19.80 | 19.66 | 19.60 | 19.57 | 19.47 | 19.30 | 19.06 | 18.95 | 20.01 | 21.53 | 20.85 | 20.59 | 20.22 | 19.66 |
| 7 | 23.46 | 23.55 | 23.67 | 23.82 | 23.80 | 23.68 | 23.44 | 23.33 | 24.65 | 26.54 | 25.70 | 25.38 | 24.88 | 24.16 |
| 8 | 26.97 | 27.35 | 27.72 | 28.00 | 28.14 | 28.12 | 27.95 | 27.87 | 29.46 | 31.76 | 30.75 | 30.38 | 29.82 | 28.91 |
| 9 | 30.28 | 30.89 | 31.58 | 32.19 | 32.52 | 32.63 | 32.54 | 32.49 | 34.37 | 37.11 | 36.04 | 35.60 | 34.95 | 33.89 |
| 10 | 33.08 | 34.10 | 35.08 | 35.99 | 36.60 | 36.97 | 37.14 | 37.20 | 39.39 | 42.58 | 41.42 | 40.93 | 40.21 | 39.02 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 47.539 | 41.420 |
| SC2 | 0 | 8 | 32.050 | 27.873 |
| SC3 | -18 | 7 | 27.240 | 23.828 |
| SC4 | -25 | 6 | 22.281 | 19.600 |
| SC5 | -34 | 6 | 22.288 | 19.796 |
| A | 3025 mm |
|---|---|
| B | 900 mm |
| C | 1260 mm |
| F | 860 mm |
| G | 1585 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3025 mm |
|---|---|
| Width | 1585 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.