Skip to Content

Unit cooler EA-DV-491GC4-A04 C

Unit cooler EA-DV-491GC4-A04 C
Illustrative photo

Producer: Karyer · Line: EA-DV (Cold Store)

Product code: EA-DV-491GC4-A04 C

Cooling capacity i
118.41 kW
Air flow
105,721 m³/h
Fin spacing
4.6 mm
Fans
4 × ⌀910 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 105,721 m³/h
External surface 521.3 m²
Inner volume 105.1 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 1,275 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 72.0 dB(A)
Sound power 96.3 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø66,7
Defrost
EA-DV-491GC4-A04 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
114.027 kW
Low speed (Y)
97.870 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 43.49 45.04 46.34 47.36 47.82 47.71 47.52 48.35 51.21 55.38 54.07 53.58 52.88 51.82
5 54.77 57.76 60.41 62.74 64.29 65.25 65.41 66.67 70.91 76.86 75.14 74.51 73.62 72.20
6 64.07 68.50 72.52 76.03 78.48 80.03 80.90 82.55 87.95 95.68 94.00 93.35 92.39 90.84
7 ≈ 72.39 78.45 84.04 88.95 92.48 94.85 96.24 98.22 104.62 113.89 111.86 111.04 109.80 107.77
8 ≈ 79.82 87.59 94.86 101.35 106.18 109.53 111.62 114.03 121.51 132.39 130.08 129.11 127.62 125.08
9 ≈ 81.59 ≈ 95.90 104.96 113.16 119.45 123.96 126.90 129.88 138.47 151.06 148.56 147.46 145.73 142.73
10 ≈ 46.42 ≈ 103.42 114.32 124.34 132.23 138.05 141.99 145.67 155.43 169.77 167.19 165.98 164.06 160.62

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 38.35 39.20 39.94 40.58 40.84 40.78 40.60 41.62 44.15 47.81 46.80 46.42 45.88 45.05
5 49.00 51.09 52.54 54.02 54.83 55.11 54.98 56.04 59.62 64.66 63.24 62.71 62.02 60.99
6 58.04 61.21 64.10 66.63 68.32 69.34 69.82 71.18 75.78 82.42 80.53 79.79 78.70 77.01
7 65.96 70.45 74.53 78.10 80.57 82.12 82.90 84.44 89.86 97.74 95.79 95.02 93.86 91.95
8 ≈ 73.15 79.06 84.48 89.25 92.65 94.88 96.08 97.87 104.16 113.34 111.03 110.03 108.50 105.95
9 ≈ 79.63 87.00 93.87 99.97 104.46 107.51 109.27 111.38 118.57 129.13 126.40 125.20 123.37 120.15
10 ≈ 85.39 94.27 102.69 110.25 115.94 119.92 122.38 124.91 133.03 144.91 141.95 140.57 138.46 134.69

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 167.191141.946
SC2 0 8 114.02797.870
SC3 -18 7 90.51879.208
SC4 -25 6 72.52464.095
SC5 -34 6 65.08658.784

Dimensions

Dimension drawing of EA-DV-491GC4-A04 C
Dimension drawing
Dimensions as drawn
A 5625 mm
B 900 mm
C 1460 mm
F 860 mm
G 1775 mm
E1 1318 mm
E2 1300 mm
E 5235 mm
D IN 1 x Ø42
D OUT 1 x Ø66,7
Overall [mm]
Length 5625 mm
Width 1775 mm
Height 1460 mm

Downloads