EA-145AG7-C01 C
9.48 kW
Defrost: Electric
Product code: EA-145AE4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,346 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 39.9 m² |
| Inner volume | 8.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 56 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-145AE4-C01 C | None |
|---|---|
| EA-145AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.87 | 4.00 | 4.11 | 4.19 | 4.22 | 4.21 | 4.16 | 4.26 | 4.54 | 4.92 | 4.81 | 4.77 | 4.72 | 4.66 |
| 5 | 4.85 | 5.10 | 5.31 | 5.48 | 5.57 | 5.58 | 5.55 | 5.64 | 5.99 | 6.49 | 6.29 | 6.23 | 6.13 | 5.99 |
| 6 | 5.68 | 6.04 | 6.36 | 6.64 | 6.78 | 6.87 | 6.90 | 7.02 | 7.46 | 8.11 | 7.89 | 7.79 | 7.64 | 7.40 |
| 7 | 6.39 | 6.88 | 7.27 | 7.65 | 7.91 | 8.07 | 8.13 | 8.26 | 8.78 | 9.54 | 9.29 | 9.18 | 9.01 | 8.72 |
| 8 | 7.02 | 7.59 | 8.16 | 8.67 | 9.02 | 9.25 | 9.35 | 9.52 | 10.11 | 10.98 | 10.69 | 10.55 | 10.34 | 9.98 |
| 9 | ≈ 7.33 | 8.29 | 9.00 | 9.64 | 10.10 | 10.41 | 10.57 | 10.77 | 11.45 | 12.43 | 12.11 | 11.95 | 11.70 | 11.27 |
| 10 | ≈ 7.29 | ≈ 8.93 | 9.79 | 10.56 | 11.14 | 11.55 | 11.78 | 12.03 | 12.78 | 13.88 | 13.54 | 13.37 | 13.09 | 12.58 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.543 |
| SC2 | 0 | 8 | 9.516 |
| SC3 | -18 | 7 | 7.768 |
| SC4 | -25 | 6 | 6.359 |
| SC5 | -34 | 6 | 5.758 |
| A | 1067 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E | 735 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1067 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.