EA-430AE6-C05 C
9.86 kW
Defrost: None
Product code: EA-145AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,176 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 38.4 m² |
| Inner volume | 11.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 66 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-145AG6-C01 C | None |
|---|---|
| EA-145AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.12 | 4.21 | 4.29 | 4.36 | 4.37 | 4.35 | 4.29 | 4.41 | 4.70 | 5.09 | 4.97 | 4.93 | 4.88 | 4.81 |
| 5 | 5.12 | 5.33 | 5.51 | 5.65 | 5.72 | 5.72 | 5.65 | 5.77 | 6.13 | 6.64 | 6.42 | 6.35 | 6.24 | 6.08 |
| 6 | 6.10 | 6.42 | 6.72 | 6.96 | 7.09 | 7.12 | 7.07 | 7.17 | 7.60 | 8.24 | 7.95 | 7.83 | 7.66 | 7.39 |
| 7 | 6.93 | 7.38 | 7.78 | 8.13 | 8.35 | 8.43 | 8.44 | 8.58 | 9.11 | 9.86 | 9.52 | 9.38 | 9.16 | 8.77 |
| 8 | 7.66 | 8.25 | 8.78 | 9.18 | 9.49 | 9.66 | 9.70 | 9.86 | 10.46 | 11.34 | 11.01 | 10.86 | 10.61 | 10.18 |
| 9 | ≈ 8.32 | 9.05 | 9.64 | 10.23 | 10.62 | 10.87 | 10.96 | 11.14 | 11.82 | 12.81 | 12.45 | 12.27 | 11.98 | 11.48 |
| 10 | ≈ 8.91 | 9.71 | 10.52 | 11.23 | 11.74 | 12.07 | 12.21 | 12.43 | 13.19 | 14.29 | 13.91 | 13.70 | 13.37 | 12.78 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.907 |
| SC2 | 0 | 8 | 9.857 |
| SC3 | -18 | 7 | 8.235 |
| SC4 | -25 | 6 | 6.715 |
| SC5 | -34 | 6 | 6.174 |
| A | 1067 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E | 735 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 1067 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.