EA-630BC6-C01 C
11.97 kW
Defrost: Electric
Product code: EA-150AG7-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,849 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 43.2 m² |
| Inner volume | 14.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 80 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 78.3 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-150AG7-C09 C | None |
|---|---|
| EA-150AG7-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.11 | 5.06 | 5.03 | 5.01 | 4.96 | 4.89 | 4.81 | 4.89 | 5.20 | 5.62 | 5.48 | 5.43 | 5.35 | 5.23 |
| 5 | 6.61 | 6.62 | 6.65 | 6.67 | 6.64 | 6.57 | 6.46 | 6.53 | 6.92 | 7.47 | 7.23 | 7.15 | 7.05 | 6.90 |
| 6 | 8.05 | 8.18 | 8.30 | 8.40 | 8.41 | 8.35 | 8.24 | 8.29 | 8.77 | 9.46 | 9.12 | 8.99 | 8.82 | 8.55 |
| 7 | 9.48 | 9.74 | 9.97 | 10.16 | 10.22 | 10.20 | 10.10 | 10.14 | 10.72 | 11.56 | 11.13 | 10.96 | 10.72 | 10.32 |
| 8 | 10.77 | 11.18 | 11.55 | 11.88 | 12.06 | 12.08 | 11.99 | 12.04 | 12.74 | 13.74 | 13.25 | 13.05 | 12.75 | 12.24 |
| 9 | 11.89 | 12.45 | 12.96 | 13.40 | 13.67 | 13.77 | 13.79 | 13.92 | 14.75 | 15.94 | 15.41 | 15.17 | 14.82 | 14.22 |
| 10 | 12.93 | 13.66 | 14.33 | 14.83 | 15.19 | 15.40 | 15.46 | 15.61 | 16.55 | 17.91 | 17.42 | 17.19 | 16.84 | 16.24 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.420 |
| SC2 | 0 | 8 | 12.043 |
| SC3 | -18 | 7 | 10.187 |
| SC4 | -25 | 6 | 8.301 |
| SC5 | -34 | 6 | 8.090 |
| A | 1237 mm |
|---|---|
| B | 740 mm |
| C | 685 mm |
| F | 545 mm |
| E | 885 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1237 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.